Step 1: Mount Interface
0-10 V interfaces must be mounted to or within a grounded,
metal ULR/NECR recognized electrical enclosure, either a
lighting fixture or a suitable UL508 listed enclosure. Follow
applicable local and national codes.
Interface must be mounted within 10 ft (3 m) of the driver it is
controlling.
WARNING - Shock Hazard. To avoid the risk of
electric shock, do not install while energized. Do not
connect any electrically live circuits to the interface
prior to installation.
1. Use the threaded mounting studs on the interface for
mounting.
2. Use the dimensioning guide below to properly mount the
interface.
3. Use provided star washer between interface and enclosure.
4. Tighten provided nuts on mounting studs.

Mounting Dimensions

B
F
G
A 4.20 in (107 mm)
B 1.00 in (25 mm)
C 3.00 in (76 mm)
D 4.90 in (124 mm)
2 | Lutron
®
EcoSystemR to 0-10 V Interface | Install Guide
C
J
E 4.60 in (117 mm)
(mounting center)
F 1.42 in (36 mm)
G 1.99 in (51 mm)
H 1.11 in (28 mm)
Step 2: Wire Interface to Driver(s)
WARNING - Shock Hazard. To avoid the risk of
electric shock, do not wire live. Interrupt power via
breaker before wiring between the interface and a
driver.
Two low-voltage and two line-voltage wires are used
between the interface and drivers. The wires are color coded
as follows:
ORANGE = Switched Hot (120-277 V~) (SH)
WHITE = Neutral (NEU)
GRAY = - 0-10 V-
PURPLE = + 0-10 V-
Use the following steps to wire an interface to a driver.
Step 2a: Line Voltage Wiring
Drivers must be selected for appropriate input voltage. Verify
that a 120 V~ driver is used only with 120 V~ mains, and
a 277 V~ driver is used only with 277 V~ mains. Interfaces
may be used at either voltage. All drivers connected to the
same interface must be rated for the same input voltage.
Interfaces can only support up to 2 A of attached driver load
current, with a maximum of 5 drivers.
1. Use 16 AWG to 18 AWG (1.5 mm² to 1.0 mm²) solid
conductors to wire between the interface and driver.
2. Wire the interface's Switched Hot (SH) (ORANGE) output to
the driver's Hot input
3. Wire the interface's Neutral (NEU) (WHITE) to the driver's
Neutral input.
Connector Location Dimensions
I
2.00 in (51 mm)
J 1.60 in (41 mm)
K 0.33 in (8.3 mm)
L 0.65 in (16.5 mm)
M 0.75 in (19 mm)
8-32 Threaded
Studs
N 1.73 in (44 mm)
O 1.33 in (34 mm)
P 0.74 in (19 mm)
Q 0.32 in (8 mm)
R 0.29 in (7 mm)
www.lutron.com/ecosystem