Gentex SSPKCLP Serie Mode D'emploi page 3

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

V. MOUNTING ROUGH-IN BOX AND RUN WIRING
MOUNTING - SPEAKER
TO GBLP BACK BOX
WALL OR CEILING MOUNT
Adjust power taps using
needle nose pliers.
Adjust intensity by inserting small flat blade
screwdriver to turn dial. Displayed number will indicate
selected candela.
NOTICE: FIELD SELECTABLE OPTIONS OF 15, 30, 75, 95
AND 115 CANDELA.
VI. CHECKOUT AND TROUBLESHOOTING
1. Supply power to the system control panel. The auxiliary signaling device should not be activated.
2. If the signal is activated:
a. Check all smoke and fire detectors in the system to make sure they have not been activated.
b. Check all wiring connections to make sure the signal detection circuits are not reversed or shorted together. Check wire color codes and traces.
3. To test the SSPKCLP Series and other signaling appliances, trip the auxiliary panel, activate alarm circuit at the main control panel or activate one of the fire detection units in the system. All
auxiliary signals should be activated.
4. An operational test on this product should be conducted in accordance with National Standards or at a minimum annually and more often if dictated by local and state codes or authorities
having jurisdiction.
SIGNALING APPLIANCE LIMITATIONS:
Your speaker meets or exceeds current audibility requirements of Underwriters Laboratories. However, if the appliance is located outside a bedroom it may not wake up a sound sleeper,
especially if the room door is closed or only partially open.
THIS APPLIANCE WILL NOT OPERATE WITHOUT ELECTRICAL POWER. AS FIRES FREQUENTLY CAUSE POWER INTERRUPTIONS,
GENTEX SUGGESTS YOU DISCUSS FURTHER SAFEGUARDS WITH YOUR LOCAL FIRE PROTECTION SPECIALIST.
VI. TO RETURN AN APPLIANCE
Should you experience problems with your appliance, proceed as follows:
1. Turn off electrical power to the auxiliary alarm circuit.
2. Remove mounting screw and slide signal off from bracket.
3. Replace unit that was removed to restore wiring supervision and to eliminate system trouble alert.
4. Carefully pack the defective unit (the manufacturer cannot be responsible for consequential damage due to shipping or mis-handling). Include your return address and complete details as to
the nature of the difficulties being experienced and date of installation.
5. Return to: Gentex Corporation, 10985 Chicago Dr., Zeeland MI 49464. Prior to returning, call the Gentex field service department at 1-800-436-8391 or e-mail FP_RMA@gentex.com to obtain
a RMA number.
SSPKCLP FIELD SELECTABLE CANDELA SELECTOR
MOUNTING -
SPEAKER/STROBE
To 4" Square x 2 1/8" Deep
METALLIC BACK BOX -
CEILING MOUNT
550-0490
Page 3

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Sspk24clp serieSspkr24 serie

Table des Matières