Electrical Specifications - Gentex SSPKCLP Serie Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

IV. ELECTRICAL SPECIFICATIONS
CLEAR Lens Strobe Current Ratings
Use with SSPK24CLP Products
Regulated 24VDC
Candela
Max. Operating
Current (mA)
15
30
75
95
115
NOTICE: DC VOLTAGE RANGE LIMITS: 16-33V. FWR VOLTAGE RANGE LIMITS: 16-33V. THIS PRODUCT WAS ONLY TESTED TO THE STATED VOLTAGE RANGE(S); DO NOT APPLY 80%
AND 110% OF THIS RANGE FOR SYSTEM OPERATION.
SYSTEM CONSIDERATIONS
1. To select the proper wattage input for the speaker, move the jumper to the appropriate pin.
2. Always maintain electrical isolation between speaker and strobe wiring on combination units.
3. Do not exceed 130% of rated speaker voltage. If excessive distortion is heard, check amplifier for signal clipping. If clipping exists, reduce either amplifier input or gain.
4. Four screws are provided, two for securing speaker to the back box and two for aesthetics. The two non-functional screws will be held in place by the pressure fit of the faceplate.
CAUTION: WHEN INSTALLING, ROUTE FIELD
WIRING AWAY FROM SHARP PROJECTIONS,
CORNERS AND INTERNAL COMPONENTS.
NOTICE: DO NOT USE LOOPED WIRE
UNDER TERMINALS. BREAK WIRE
RUN TO PROVIDE SUPERVISION OF
CONNECTION.
*MAX. WIRE DISTANCE (IN FEET) =
* INCLUDES WIRE TO AND FROM APPLIANCE.
ASSUMES ALL APPLIANCES ARE AT THE END OF WIRE RUN (WORST CASE).
CAUTION: APPLIES ONLY TO REGULATED SUPPLIES.
NOTICE: ALL STROBES ARE DESIGNED TO FLASH AS SPECIFIED WITH CONTINUOUS APPLIED VOLTAGE. THIS APPLIANCE IS NOT RECOMMENDED FOR USE ON CODED OR
PULSING SIGNALING CIRCUITS. HOWEVER, USE OF THE AVSM CONTROL MODULE IS PERMITTED TO SYNCHRONIZE THE STROBE.
NOTICE: REFERENCE AVSM CONTROL MODULE MANUAL (550-0284, DATED 2-1-03) FOR SYNCHRONIZATION MODULE WIRING DIAGRAMS. AVSM MANUAL CAN BE OBTAINED AT
HTTP://WWW.GENTEX.COM OR CALL GENTEX CORPORATION AT 1-800-436-8391.
SSPKR24C PRODUCT INFORMATION
Regulated 24VFWR Max.
Operating
Current (mA)
120
190
120
191
200
277
220
298
290
418
Field Selectable Power Tap Selection - Reverberant (dBA @ 10ft.)
Voltage
1/8 Watt
1/4 Watt
25 Volts
74.6
70.7 Volts
73.7
PANEL VOLTAGE - DEVICE MINIMUM VOLTAGE
TOTAL CURRENT DRAW
Candela
15
30
75
95
115
1/2 Watt
1 Watt
77.7
80.5
83.1
76.7
79.6
82.5
Model
Color Lens
SSPKR24C
Red
RED Lens Strobe Current Ratings
Use with SSPKR24C Products
Regulated 24VDC
Regulated 24VFWR Max.
Max. Operating
Current (mA)
128
128
225
235
341
2 Watt
4 Watt
85.6
87.9
85.4
87.9
X WIRE CONDUCTIVITY (STROBE ONLY)
Operating
Current (mA)
220
220
306
402
444
550-0490
Page 2

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Sspk24clp serieSspkr24 serie