Electrical Operation - hager HIC4 Serie Notice D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Operation

Electrical operation

Power Supply
The products integrate 2 power inputs (101-102, 201-202),
and consider the available source to keep the product
operational.
Control Logic
The products are electrically driven by external volt free
contacts between terminals 314 and 317. This command
can be inhibited: terminals 313-317 opened.
Two types of control logicare possible: impulse or
contactor. The choice of the control logic is made via
programming (refer to programming chapter).
Impulse logic (standard configuration)
• The switching command is a pulsed dry contact lasting
at least 30ms.
• When the order disappears, the product remains
inposition
• The impulse can be of infinite duration without causing
any disturbance.
47
All manuals and user guides at all-guides.com
Contactor logic
• The transfer command is a maintained dry contact
• If command I or II disappears, the device returns to zero
position
• A 0 command drives the device into zero position,
irrespective of the status of the I and II commands (1 or 2).