Operation
Control circuits
Denomination
Terminals
Power supply 1 Power 101
230 V~102
Power supply 2 Power 201
230 V~202
Sensing inputs
N (103)
source 1
L3 (104
L2 (105)
L1 (106)
Sensing inputs
L1 (203)
source 2
L2 (204)
L3 (205)
N (206)
Commands
207
208
209
210
Genset (1)
73
start signal
74
Control
313
(Impulse/
contactor
314
mode to
change
315
programming)
316
317
Remote
RJ
interface
connection
Position
13
auxiliary
14
contacts
24
34
Auxiliary
43
contacts
44
/ AUT &
53
Padlock
54
Fault
63
relay
64
Voltage and frequency sensing precision:1%
Refer to programming, Setup, to modify relay state.
(1)
44
All manuals and user guides at all-guides.com
Description
Source 1
Source 2
Neutral
Phase 3
Phase 2
Phase 1
Phase 1
Not connected
Phase 3
Not connected
Commands inputs Common terminal
Backup source transfer control input (CTS)
Remote test on load input
DC power supply
Genset start/stop relay - 2 stable positions
Programmable state - factory setting =NO,
close to start
Control activation
if closed with 317
Position 2 order if closed with 317
-
Position 0 order if closed with 317
Specific voltage supply
Common control terminals 313 to 316
Remote interfaces connection
Common I - 0 - II
AC position I NO
AC position II NO
AC position 0 NO
Auto/manu selector position
Closed in automatic position
Padlocked information
Closed if padlock is in place
Relay closed when product is faulty
(if product is powered)
Characteristics
Recommended
section
220 à 240 Vac
1,5 mm
±20%
500 Vac (phase-
1,5 mm
phase) maximum
288 Vac
(phase-neutral)
maximum
500 Vac (phase-
1,5 mm
phase) maximum
288 Vac
(phase-neutral)
maximum
q
1,5 mm
Do not connect
to any
power supply
Dry contact
4 mm
2
5A AC1/250 V
q
1,5 mm
Do not connect
to any
power supply
Maximum
RJ45 8/8
distance 3m.
5A AC1/250 V
1,5 mm
5A AC1/250 V
1,5 mm
5A AC1/250 V
1,5 mm
2
2
2
2
2
2
2
2