Wiring diagram
Technical information SOLO – 12 June 2008 – V1.0
Wiring diagram
1) Connecting the reader to an ACCESS IT control unit via an RS485 bus
Data sheet:
(?)
4 wires (3 pairs recommended)
1200 m
0.6 mm (SYT recommended)
±
Characteristic:
Sensitive connection
Screen:
Recommended
To achieve 1200 m, you need to install a 220Ω resistor at each end of the network between points A and
B (see above).
Note:
The total length must not exceed the recommended distance.
ACCESS IT Unit
Note:
The 12 V outputs on the control unit
must not exceed 0.5 A. If you wish to
connect two SOLOs, take the power directly
from the „Power Supply‰ terminal block.