Contents
- Burner description
BLU 1500.1 LN PR TC - SGT 230-400-50 BT330
RANGE NAME BY FUEL TYPE
BLU
Gas
MODEL SIZE (Gas: kW; Oil: kg/h)
BLU 1500.1 1550 kW
EMISSIONS
-
Standard Class 2 - GAS EN676 (<120 mg/kWh)
LN Low NOx Class 3 - GAS EN676 (<80 mg/kWh)
OPERATION TYPE
PAB
2 stages soft start
PR
2 stages progressive mechanical
E
2 stages modulating electronic
HEAD TYPE
TC
Short head
TL
Long head
FUEL
GN
Gas natural
LPG
Liquid gas
BIOGAS
Biogas
EQUIPMENT
SGT
Separate gas train
ELECTRICAL POWER SUPPLY
230-400-50
230-400 Volt, 50 Hz
CONTROL BOX
BT330
Lamtec
Scope of delivery
The burner is delivered in a modular system of
packagings i.e. separate set/box:
BBCH: Burner Body with Combustion Head
with flange.
- 1 bag including : - multilanguage technical manual.
- spanner.
- screws, nuts and washer.
GT: separate Gas Train
KIT & ACS are managed and delivered separately
420010514602
15
M1
A1
BT3XX control unit
A4
Display
F6
Air pressure switch
F7
Gas pressure switch
M1
Electric motor
T1
Ignition transformer
Y10
Servomotor for air
Y11
Servomotor for gas
3
Air regulation in the burner head
5
Housing
8
Blast tube
10
Wieland socket
15
Burner flange
16
Reset key
113
Air intake
KIT & ACS delivered separately
www.ecoflam-burners.com
EN