Wiring
1.
Pull service wires through mounting arm and into
housing approximately 10" .
2.
a. Three-terminal block (2-wire service): Connect line
service lead to terminal that is connected to black
factory-installed wire. Connect neutral service
wire to terminal that is connected to white factory-
installed wire.
b. Three-terminal block (3-wire service, 2 lines,
1 ground): Connect 1 line service lead to terminal
that is connected to black factory-installed wire.
Connect other line service lead to terminal that is
connected to white factory-installed wire. Connect
ground service lead to terminal that is connected
to green factory-installed wire.
c. Three-terminal block (3-wire service, 1 line, 1
neutral, 1 ground): Connect line service lead
to terminal that is connected to black factory-
installed wire. Connect neutral service wire to
terminal that is connected to white factory-
installed wire. Connect ground service wire to
terminal that is connected to green factory-
installed wire.
d. No terminal block (3-wire service, 2 lines, 1
ground): Connect 1 line service lead to black
factory-installed wire. Connect other line service
lead to white factory-installed wire. Connect
ground service lead to green factory-installed
wire.
e. No terminal block (3-wire service, 1 line, 1 neutral,
1 ground): Connect line service lead to black
factory-installed wire. Connect neutral service
wire to white factory-installed wire. Connect
ground service wire green factory-installed wire.
3.
Position and secure all wires away from all other
electrical components (drivers, terminal blocks).
4.
Close access door and secure latches.
Arm Installation (Square Pole) FIG. 3
Tools Required
1/2" open wrench, Phillips screw driver.
1.
Insert nut plate into pole aligning holes on nut plate
with mounting holes on the pole.
2.
Insert threaded rods through top and bottom holes
and screw them into nut plate.
3.
Pull wires through center hole of back up plate and
center hole of pole.
4.
Make electrical connections between wires from
pole and wires from the fixture.
Navion
LED Area/Site Luminaire Installation Instructions IMI-812 ADH140462 www.eaton.com
TM
Navion
LED Area/Site Luminaire Installation Instructions
TM
5.
Align top and bottom holes on the arm to slide over
threaded rods. Arm should be flush to the surface of
the pole.
6.
Push washers over the threaded rods and screw on
nuts.
7.
Using 1/2" open wrench tighten nuts.
8.
Pass cover plate over arm. Align set screw holes on
the cover and the arm and tighten set screw.
FIG. 3
Cover Plate
Arm
Arm Installation (Round Pole) FIG. 4
Tools Required
1/2" open wrench, Phillips screw driver.
1.
Insert nut plate into pole aligning holes on nut plate
with mounting holes on the pole.
2.
Insert threaded rods through top and bottom holes
and screw them into nut plate.
3.
With the rounded end of the adapter facing the pole,
align the holes on the adapter with mounting holes
on the pole. Push adapter over threaded rods.
4.
Pull wires through center holes nut plate, pole and
adapter and make wiring connections.
5.
Align top and bottom holes on the arm to slide over
threaded rods. arm should be flush with the flat
surface of adapter.
6.
Push washers over the threaded rods and screw
on nuts.
7.
Using 1/2" open wrench tighten nuts.
8.
Pass cover plate over arm. Align set screw holes on
the cover and the arm and tighten set screw.
Threaded Rods
Nuts
Washer
Electrical Wires
Square Pole
Backup Plate
3