1.8 MANTAINANCE

1.8.1 ROUTINE MAINTENANCE

Cleaning of the fi lter is carried out with the frequency of at least once a month and anyhow according to the
degree of dustiness of the installation environment.
Remove the metal grille, positioned in the front part (Ref. A) by rotating the screw by one fourth of a revolu-
tion in the anticlockwise direction and pull out the fi lter. Clean the fi lter by washing it with lukewarm water.
CAUTION: Do not use hard brushes or blunt instruments to avoid damaging the fi lter.
Reposition the fi lter and close the metal grille by turning the screw anticlockwise by one fourth of a
revolution.
2
DISADVANTAGES, CAUSES AND REMEDIES TABLE
Problem
The display does not
light up
Insuffi cient
water
cooling
Insuffi cient
water
heating
On the display ap-
pears the message
"E1"
On the display ap-
pears the message
"E2"
On the display ap-
pears the message
"AL1"
The temperature dis-
played is not the real
one
C H I L L E R L I N E
Cause
Lack of electric supply
Insuffi cient water fl ow.
Insuffi cient insulation.
Dirty air fi lter
Ambient temperature too
high
Outgoing air from the
ventilation grid at room
temperature
Obstructed
ventilation
grate
Broken ventilation system Contact the TECO S.r.l area retailer or distributor
Insuffi cient water fl ow
Faulty heater
Damage of the water's
temperature probe
Damage of the overheat-
ing temperature probe
Dirty air fi lter
Room temperature is too
high
Obstructed
ventilation
grille
Failed ventilation system Contact the TECO S.r.l area retailer or distributor
The water does not circu-
late correctly inside the
hydraulic circuit
Long and not insulated
pipes
Temperature sensor not
calibrated correctly
Check that the plug is fully inserted in the electrical current sock-
et.
Check that the switch is in position "1"
Check the proper operation of the pump (not supplied)
Insulate the walls of the aquarium and the pipes to reduce heat
loss
Clean the air fi lter following the instruction (Chapter Maintenance)
Re-establish the optimal ambient conditions
The maximum ambient temperature allowed is 38°C (100°F)
Lack of gas in the compressor, contact the TECO S.r.l area retai-
ler or distributor
Free the grate or place the unit in a suitable ambient
Check the correct operation of the pump (not supplied)
Contact the TECO S.r.l area retailer or distributor
Contact the TECO S.r.l area retailer or distributor
Contact the TECO S.r.l area retailer or distributor
Clean the fi lter as indicated in Chapter 6, Maintenance
Restore the optimal environmental conditions. The maximum al-
lowed room temperature is 38 °C (100 °F)
Release the ventilation grille or place the air-conditioner in a suit-
able environment
Check eventually pipes obstructions
Check the effi ciency of the aquarium's pump (not supplied)
Reduce the pipe lenght as much as possible, and insulate them
Calibrate the temperature sensor as described in paragraph
1.5.4 Thermostat Settings
Tab. 2-1
Remedy
EN
11