14.1.2 Parameters related to Relay Output
Rel.UNi
Rel.FUN
coNtac.
setP.
setP.lo
setP.Hi
act.DiR
HYst
14
9116 UNiVeRsal coNVeRteR
Relay Units (for iN.tYPe ≠ teMP):
PeRc = Relay setpoint in percent of input range.
DisP = Relay setpoints and hysteresis values relates to DisP.lo
and DisP.Hi (display units)
Relay Function:
oFF (Note 3 ) = Relay is always oFF
PoW (Note 3 ) = Relay is always oN if power is applied
eRR = Relay is activated when sensor error is present
WiND = Relay is activated when input signal is between setP.
lo and setP.Hi values
setP = Relay is activated when input signal reaches setP
value
Relay contact function:
N.c. = Normaly closed relay contact (for Rel.FUN = setP)
N.o. = Normally open relay contact (for Rel.FUN = setP)
o.i.W = Relay contact open inside Window (for Rel.FUN =
WiND)
c.i.W = Relay contact closed inside Window (for Rel.FUN =
WiND)
Relay setpoint value in Rel.UNi units for iN.tYPe ≠ teMP or
in UNit for iN.tYPe = teMP. (for Rel.FUN = setP)
Relay setpoint low value in Rel.UNi units for iN.tYPe ≠ teMP
or in UNit for iN.tYPe = teMP. (for Rel.FUN = WiND)
Relay setpoint high value in Rel.UNi units for iN.tYPe ≠ teMP
or in UNit for iN.tYPe = teMP. (for Rel.FUN = WiND)
Relay action for increasing or decreasing input signal
(for Rel.FUN = setP):
DecR = Relay activates when input signal ≤ setP.
iNcR = Relay activates when input signal ≥ setP.
Hysteresis value in Rel.UNi units for iN.tYPe ≠ teMP or in
UNit for iN.tYPe = teMP. (for Rel.FUN = setP or WiND)
Version No. V2R0