Temperature - Centrometal CSK-Touch Instructions Techniques

Masquer les pouces Voir aussi pour CSK-Touch:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 39
All manuals and user guides at all-guides.com
ENG
Shedule, temperature
1.x.x. Table 1/2/3
Table for selecting the time when the boiler is active and when not. Green at the left edge of the
table indicates the start of time from when the boiler is active for heating, and red at the edge of the
Table indicates the start of time when the boiler is not active for heating. On each day of the week it
is possible to select 3 times the active state of the boiler and 3 times the time when the boiler is not
active for heating. The factory settings of the tables are: every day from Monday to Sunday from
06:00 hours the boiler is active for heating until 22:00 from when the boiler starts to be inactive until
the next day at 06:00. On the right side of the screen there are buttons to copy the desired day and
paste it to another selected day (copy / paste).
1.X. DHW
1.x.x. DHW schedule
Selecting a time when DHW is active on a particular day of the week - time schedules can be
switched off or on, and when switched on,
the DHW heating activity times in the table
must be set.
1.x.x. Table
Table for selecting the time when DHW heating is active and when not.
Factory:
Table 1
06:00-22:00

2. TEMPERATURE

Depending on the configuration selected on the boiler, certain menus appear in the menu
2.Temperature in which the set temperatures and differentiations (seen on the boiler control) can
be changed:
Day / Night Temp. / Daily room temp. / Night room temp. / Heating curve / Correction coeff. / Buffer
tank temp. / Min. buf. tank temp. / Diff. buf. tank temp. / Diff. stop buff. tank / Crossover temp. / DHW
temp. / Differential of DHW
2.1. View A
2.1.1. Day/Night Temp.
Day Temperature: maintaining a set daily temperature all the time
Night temperature: maintaining a set night temperature all the time
Table 1/2: Maintain day / night temperature by set times for each day of the week of the selected
table
Technical instructions CSK-Touch
setting
mon/tue/wed/thu/fri/sat/sun
Factory:
DHW schedule
Table for selecting the time when DHW heating is
active and when not. The green color on the left
edge of the table indicates the start of time since
DHW heating is active, and the red color on the
edge of the table indicates the start of time when
DHW heating is not active. On each day of the week
it is possible to select 3 times the active DHW
heating status and 3 times the time when the DHW
heating is not active. The factory default settings for
the table are: every day from Monday to Sunday
from 06:00 hours DHW heating is active until 22:00
from when DHW heating starts to be inactive, until
the next day at 06:00. On the right side of the screen
there are buttons to copy the desired day and paste
it to another selected day (copy / paste).
Factory:
Day/Night Temp
setting
OFF
OFF / ON
setting
Day Temp.
Day Temp. / Night / Table 1/2
33