Digital Output(S); Relay Outputs; Status Indication - PR electronics 5223 Mode D'emploi

Masquer les pouces Voir aussi pour 5223:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

standard voltage output (pin 12) is obtained by leading the current signal (pin
13) through an internal shunt resistor (pin 12). At voltage signals in the ranges
0...1 VDC, a 50 Ω shunt (JP1) is applied; in the ranges 0...10 VDC, a 500 Ω shunt
(JP2) is applied.

DIGITAl OUTPUT(s)

The action on the outputs can be inverted, and the hysteresis can be set acc. to
your specifications.
At power up, shifts on the outputs can be delayed for up to 999 s.
NPN and PNP outputs for external relay, electromechanical counter, PLC input,
or equivalent load.
The outputs are current-limited by way of PTC resistors.

RElAy OUTPUTs

The PRecon 5223 can be delivered with 2 relay outputs that are programmed
individual ly.

sTATUs INDICATION

The 5223 is equipped with 5 front LEDs.
f1 and f2 in:
Dig. out. 1 and 2:
Error:
Indicates an active input (non-active at NPN input).
Indicates active output.
Programmable by use of PReset to indicate sensor
errors.
25

Publicité

Table des Matières
loading

Table des Matières