Wiring Details
Electrical Wiring
Network Wiring
Network wiring is no different than simple wiring, except that all units
are wired together in a "daisy-chain". The EOL jumper must be
enabled on the last unit in the chain.
IAQPoint Network Wiring Diagram
This drawing applies to units configured with either Modbus, FLN or
BACNet communication.
V+
Next
JP7
V-
V-
Previous
V+
Power and communication wires are connected from one unit to the
next unit in the "chain", as illustrated in the drawing: the wires come in
to the unit from the "previous" unit and can be wired from that unit to the
"next" until the network is complete.
LON (TP/FT10) communication connections are not polarity sensitive.
Please consult the Echelon documentation for further LON connection
details (http://www.echelon.com/support/documentation/manuals/
routers/078-0167-01B.pdf).
18
All manuals and user guides at all-guides.com
D6
D3
Shield
IAQPoint User Manual
Honeywell
B
Next
A
A
Previous
B
RS-485 COMMUNICATION
Communication Wire Gauge:
2-24 AWG (Belden 9841)
Twisted and shielded cable
2000 feet (600 m) per channel
T-tap: 65 feet (20 m) / T-tap
130 feet (40 m) total
511838
11/07