Electrical Wiring
Electrical and communication wiring is achieved through terminals
located at the back of the unit. There are also two separate jumpers that
allow users to configure the detection range and end-of-line settings.
Configuring the End-of-Line
This option applies only to units configured with either Modbus, FLN or
BACNet communication.
The end-of-line jumper lets users configure the unit's end-of-line,
according to which pins are selected, as shown in the image below.
IAQPoint Wiring Diagram
JP7
0 – 2000 ppm
JP7
0 – 10000 ppm
V-
V+
511838
11/07
Wiring Details
JP8
JP7
JP5
D6
D3
Shield
IAQPoint User Manual
Honeywell
Wiring Details
Electrical Wiring
EOL Positions
R
JP8
RC
JP8
JP8
No end-of-line
COMMUNICATION
Communication Wire Gauge:
A
2-24 AWG (Belden 9841)
Twisted and shielded cable
B
2000 feet (600 m) per channel
T-tap: 65 feet (20 m) / T-tap
130 feet (40 m) total
17