Control panel for 1 hydraulic bollard HYDRA serie.
Terminals
L-N-GND
1-2-3
6
DOWN
UP
PHOT
STOP
COM
P.P.
24 VAC
SCA
SHIELD-ANT
Note:
The control unit uses a "P2" key with the same functions of the Step-by-Step push-button. This is useful
to control the automatic system during installation (only with DIP2: OFF).
TW
It allows the maximum duration of raising and lowering.
It must be preset approx. 4s more with respect to the actual stroke time of the system.
The adjustment ranges from 6s to 18s maximum.
TCA
If activated , by meand of DIP 1, it allows to adjust a delay time for the automatic raising of the
bollard .
The adjustment ranges from 3s to 90s maximum.
CONTROL PANEL HY.CELL
Function
Description
Input, 230VAC 50Hz (HY.CELL)
Power supply
Input, 115VAC 50/60Hz (HY.CELL 115V))
(1-Phase/2-Neutral/GND-Ground connection)
Connection to the motor:
Motor
(1-lowering/2-common /3-raising)
Inf
Connection bollard status
Lowering command input (N.O. contact.),
DOWN
programmable as clock contact
UP
Raising command input (N.O. contact)
PHOT
Safety devices input , N.C. contact (photocells, loop detectors ).
STOP
Input, STOP key (N.C. contact)
COM
Common, all control inputs.
Input, step-by-step key (N.O. contact).
Step-by-Step
In "Service man" mode, it activates the DOWN control function.
24Vac
Output, 24Vac/200mA max accessory power supply.
Not insulated potential clean contact for the connection of a war-
SCA/SYREN
ning light or an acoustic device.
See also DIP 4 functions
Connection of the antenna to the incorporated radio-receiver module
Antenna
(SHIELD-screen/ANT-signal).
TRIMMER FUNCTIONS
WIRE DIAGRAM
11