• Continuos storage of planned and reached values by each channel (limits and
historic highs).
• Dielectric isolation: 2.5 Kv for 60".
• Software configuration to control the environment temperature.
• Resolution 1° C.
• Working temperature of device from -40°C to 60°C.
• Max allowed dampness in the room 90% not condensing.
• Electrical connections with fast polarised connectors.
• Possibility of manual relays switch through menu test relays to simulate and check
the reliability of contact.
• Technical manual in five languages (and more on request).
• Construction in accordance with rules
• Input filter for power supply in accordance with rules
• Tropicalization (optional).
Perform a square hole measuring 91x91 mm in the panel board sheet.
Fasten the monitoring system trough the special hooks.
The device can be supplied with (24÷240) Volt AC/DC ± 10% 50/60 Hz without
respect of polarity.
Perform the connections on the terminal board following the scheme on TAB1 at the
end of this manual.
FAULT relay usually results excited during normal working of device (FAULT STATUS
A, TAB 1), in case of failure of probes or feeding absence, the relay switch off (FAULT
STATUS B, TAB 1).
FAN relay is dedicated to the management of the fans of cooling of the transformer or
for the conditioning of the environment where the transformer is installed.
All manuals and user guides at all-guides.com
.
ASSEMBLY
POWER SUPPLY
ELECTRICAL CONNECTIONS
- 11 -