Télécharger Imprimer la page

Technical Specifications - Johnson Controls VA9308-A-Z Serie Mode D'emploi

Publicité

VA9308-Axx-xZ / VA9310-xxx-x

Technical specifications

Product code
• Code produit • Produktcode
• Codice prodotto • Código de producto
• Productcode • Produktkod • Kód výrobku
• Kod produktu • Код продукта
• Código de produto • 产品代码 • 製品コード
Control type
• Type de commande • Steuerungsart
• Tipo di comando • Tipo de control
• Besturingstype • Kontrolltyp • Typ řízení
• Typ sterowania • Тип управления
• Tipo de controlo • 控制类型 • 制御タイプ
Power
Transformer:
(Class 2 or SELV)
Input
• Entrée • Eingang • Ingresso • Entrada
• Ingang • Ingång • Vstup • Wejście
• Вход • Entrada • 输入 • 入力
Impedance (±3%)
• Impédance • Impedanz • Impedenza
• Impedancia • Impedantie • Impedans
• Impedance • Impedancja • Импеданс
• Impedância • 阻抗 • インピーダンス
Feedback
• Rétroaction • Rückmeldung • Ritorno
• Realimentación • Feedback • Feedback
• Zpětná vazba • Sprzężenie zwrotne
• Обратная связь • Feedback • 反馈
• フィードバック
Torque
M
Rotation
range
Rotation
time
Compliance
VA9310-HGA-1
On/Off,
Proportional
Floating
AC 24 V ±20%,
50/60 Hz: 6.2 VA
DC 24 V ±10%: 1.9 W
≥6.5 VA
DC 0(2)...10 V,
0(4)...20 mA with
field furnished 500
AC 24 V
Ω resistor,
±20%
Offset:
DC 24 V
DC 0...10 V
±10%
Span:
DC 2...10 V
Voltage Control:
100 kΩ
100 kΩ
Current Control:
0.5 kΩ
DC 0(2)...10 V
35 sec
United States: UL Listed, CCN XAPX, File E27734; to UL 60730-1: Automatic Electrical Controls for Household and Similar Use,
Part 1; and UL 60730-2-14: Part 2, Particular Requirements for Electric Actuators. Plenum Rated (UL 2043). Suitable for use in
Other Environmental Air Space (Plenum) in accordance with section 300.22 (c) of the National Electrical Code.
Canada: UL Listed, CCN XAPX7, File E27734; to CAN/CSA E60730-1:02: Automatic Electrical Controls for Household and
Similar Use, Part 1; and CAN/CSA-E60730-2-14, Particular Requirements for Electric Actuators.
Europe: CE Mark
Johnson Controls declares that these products are in compliance with the essential requirements and other relevant provisions of
the EMC Directive and Low Voltage Directive.
Australia and New Zealand: RCM Mark, Australia/NZ Emissions Compliant
VA9310-HGA-2
On/Off,
Proportional
Floating
AC 24 V ±20%,
50/60 Hz: 4.7 VA
DC 24 V ±10%: 1.3 W
≥5.0 VA
DC 0(2)...10 V,
0(4)...20 mA with
field furnished
AC 24 V
500
±20%
Ω resistor,
DC 24 V
Offset:
±10%
DC 0...10 V
Span:
DC 2...10 V
Voltage Control:
100 kΩ
100 kΩ
Current Control:
0.5 kΩ
DC 0(2)...10 V
10 Nm (90 lb∙in)
Mechanically limited 35°..95° ±3° in 5° increments
90 sec
12
VA9310-HGA-3
On/Off,
Proportional
Floating
AC 24 V ±20%,
50/60 Hz: 4.7 VA
DC 24 V ±10%: 1.3 W
DC 0(2)...10 V,
0(4)...20 mA with
field furnished 500
AC 24 V
Ω resistor,
±20%
Offset:
DC 24 V
DC 0...10 V
±10%
Span:
DC 2...10 V
Voltage Control:
100 kΩ
100 kΩ
Current Control:
0.5 kΩ
DC 0(2)...10 V
90 sec
34-636-2421 Rev. M
VA9310-
VA9310-
GUA-1
GUA-2
Proportional
Nominal AC
Nominal AC
120 V, 60 Hz:
230 V, 50/60
0.05 A
Hz: 0.05 A
DC 0(2)...10 V,
0(4)...20 mA with field
furnished 500 Ω resistor
Voltage Control: 100 kΩ
Current Control: 0.5 kΩ
35 sec
90 sec

Publicité

loading

Ce manuel est également adapté pour:

Va9310 serie