Vaisala CAB100 Guide Rapide page 18

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 41
3. Strip approximately 100 mm (4 in) of the cable, and cut the phase and neutral wires to the
length of approximately 50 mm (2 in). If you are using a stranded wire, add cable ferrules
to the ends.
CAUTION!
and neutral wires. Under mechanical stress, the grounding wire must be the
last to disconnect from the protective ground terminal.
Number
Wire
in figure
1
Phase L
2
Neutral N
3
Grounding
PE/GND
18
Make sure that the grounding wire is longer than the phase
Wire color
Wire color
(international)
(North America)
Brown
Black
Blue
White
Yellow/Green
Green
50 [1.97]
100 [3.94]
Min. ... max. wire cross-section
Solid wire:
2
0.75 ... 4 mm
(18 ... 12 AWG)
Stranded wire:
2
0.75 ... 2.5 mm
1
2
3
mm
[in]
(18 ... 14 AWG)
M212284EN-D

Publicité

Table des Matières
loading

Produits Connexes pour Vaisala CAB100

Ce manuel est également adapté pour:

Cab100aCab100b

Table des Matières