when machine is recovering refrigerant.
1. Check pressure on recovery machine inlet pressure gauge. Pressure must be below 0,7 Bar (10 PSI), but above 0,1 Bar
(2 PSI).
2. Insert short yellow hose into the "plastic bottle with two openings" which is supplied. Carefully attach the short yellow
hose to the oil drain fitting on the recovery machine. As hose is tightened on fitting, oil will flow into container. (Hose is
equipped with a depressor which will open core valve in oil drain fitting).
3. When oil has drained completely, disconnect the hose from the system. Unscrew the cap/hose from the bottle and
dispose of the oil into an environmentally approved manner.
MAINTENANCE REQUIREMENTS
1. Replace filter if sight glass indicator is red/orange in color (as a reference, when about 7 kilos is refrigerant recovered.)
The color change may be green/blue for dry condition when refrigerant is passing thru and red/orange in color for wet
condition.
2. Replace filter after recovering refrigerant from a known contaminated system.
3. Replace filter if excessive pressure drop is indicated. Difference of pressure gauge reading before and after filter.
������� ��
����
�������������
�� ������� ������ ���� ����
�������� �� ��� ��������� ���
�������� ��������
10
��� ����
���� ����
����������� ��� ������������ �������� ����� �������� ����� ����