Combustion Adjustment; Nozzles Recommended - Riello Burners 40 G5R Manuel D'entretien

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

COMBUSTION ADJUSTMENT

In conformity with Efficiency Directive 92/42/EEC the application of the burner on the boiler, adjust-
ment and testing must be carried out observing the instruction manual of the boiler, including verifica-
tion of the CO and CO
temperature of the water in the boiler.
To suit the required appliance output, fit the nozzle then adjust the pump pressure, the setting of the
combustion head and the air damper opening in accordance with the following schedule.
Nozzle
1
GPH
Angle
0.60
60°
0.65
60°
0.75
60°
0.85
60°
1.00
60°
1.10
60°
1.25
60°
1

NOZZLES RECOMMENDED

2
PRESSURE :
3
COMBUSTION HEAD SETTING : This is done when fitting the nozzle, with the blast tube
Terminal plane of the blast tube
Blast tube
D5582
2347
All manuals and user guides at all-guides.com
concentration in the flue gases, their temperatures and the average
2
Pump pressure
Burner output
2
bar
12
12
12
12
12
12
12
: Monarch type R - NS
Delavan type W - A - E
Steinen type Q - H
Danfoss type B - H
: The pump leaves the factory set at this value
12 bar
removed. It depends on the output of the burner and is car-
ried out by rotating the regulating rod, till the terminal plane
of the blast tube is level with the set-point, as indicated in
the schedule.
2
5
3
1
Regulating rod
Shutter
Comb. head
adjustment
kg/h ± 4%
Set-point
2.3
2.5
2.9
3.3
3.9
4.3
4.9
In the sketch on the left, the combustion
head is set for an output of 0.85 GPH at
12 bar, while the shutter is level with set-
point 2,5, as required by the above
schedule.
5
GB
Air damper
adjustment
3
4
Set-point
1
2
1,5
2
2
2,5
2,5
3
3,5
3,5
4
4,5
6
7

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

3744612

Table des Matières