Outdoor connections FOGGY 30
Insert an easily accessible 16 A C-curve multi-pole mains switch and having a minimum distance between the
contacts of at least 3 mm in the electrical installation of the building.
For electric network power supply input, use double insulation cables.
Input for connecting to the
activation system
Network connection
E
Passing power
N
supply cables
G
Connections to the security system
Input for network power
supply connection
N
L
The twisted wires must not be consolidated
with a weld in the points where they are
subject to contact pressure.
- 42 -
F 3
(1 L - Phase 230V ~
(2) Earthing - Input
for earthing
(3) N - Neutral 230V ~
Block the power supply
cable to the predefined
fastening point using the
supplied cable gland
The TAMPER wires must
be installed so that they do
not come into contact with
mains-powered
otherwise they must be
directly tubed.
Passing
control and
signal cables
Block the cables to
the
predefined
fastening points
using suitable strips
to ensure they do
not
come
contact with mains-
powered parts.
parts,
into