RCPC Partition Control Interface
Overview
The RCPC partition control interface is a separate plenum rated low voltage control box that will automatically reconfigure the
space lighting controls based on when movable walls are open or closed.
The RCPC coordinates lighting control for up to four Room Controllers or DLVP Power Modules (DLVP PM) based on the
position of up to four movable walls equipped with Cooper Lighting Solutions IRTR sensors.
Requires no software change to existing Room Controllers or DLVP Power Modules.
Specifications
Compatible Systems
Room Controller
DLVP
Connections
• Four RJ45 wallstation ports
• Four occupancy RJ45 sensor ports
• Four IRTR or partition position switch input terminals
Input Voltage
24VDC from the Room Controller or DLVP panel
Operating
• Temperature: 32°F to 104°F (0°C to 40°C)
Environment
• Relative humidity: 0-90%, non-condensing
• For indoor use only
Construction
Enclosure: powder coated steel
Enclosure Size
6.1" W x 11.1" L x 2.8" D
155mm W x 282mm L x 71mm D
ROOM A
Room Controller
or
DLVP PM A
Room Controller
or
DLVP PM D
ROOM D
The diagram shows an example four room configuration using the RCPC partition control interface. Note two room, three
room and four room configurations can be supported. Either an IRTR or a contact closure/switch can be used to detect the
presence or absence of the wall between two adjoining rooms or spaces.
2
www.cooperlighting.com
Room A WS
Room A Occ
RCPC
A
B
C
IRTR D | A
Wallstation
Partition
Occupancy
Room D Occ
Room D WS
Room B WS
Room B Occ
IRTR A | B
D
IRTR B | C
Room C Occ
IRTR D | C
ROOM B
Room Controller
or
DLVP PM B
Room Controller
or
DLVP PM C
ROOM C
Room C WS

Publicité

Table des Matières
loading

Table des Matières