Operator: Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY
BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE
PERSONAL INJURY AND/OR PROPERTY DAMAGE.
The Type 1050 Indoor-Outdoor Control is designed for use on
conventional hot water heating systems where it is desired to
vary boiler temperature according to outdoor weather condi-
tions. These controls are not recommended for radiant panel
installations because of the lower boiler temperatures required.
Type 1050 has open-on-rise (SPST) switch action.
This indoor-outdoor control increases or decreases frequency
of burner operation to maintain a proper balance between boiler
temperature and outdoor temperature. This control should
always be used with a separate high limit control.
For increased flexibility, this control has two simple adjustments
that enable it to be set to meet the needs of almost any
installation. The square dial is used to adjust the reset ratio from
1-1/2 to 1, up to 1 to 1-1/2. The round dial permits additional
adjustment, if necessary, to raise or lower boiler water tempera-
ture at all outdoor temperatures.
THIS CONTROL MUST BE INSTALLED BY A QUALIFIED
INSTALLER.
Do not exceed the specification ratings.
All wiring must conform to local and national electrical
codes and ordinances.
This control is a precision instrument, and should be
handled carefully. Rough handling or distorting compo-
nents could cause the control to malfunction.
This control has been accurately calibrated at the factory.
Any attempt to calibrate this control will void the White-
Rodgers warranty.
ELECTRICAL DATA
Switch Action:
Open on Rise
Switch Rating: S.P.S.T.
14F.L.A.,
84L.R.A., 120V.A.C.
7F.L.A., 42L.R.A., 240V.A.C.
5.6A.,@ 25V, 120V.A.C.
2.8A.,@ 240V.A.C.
WHITE-RODGERS DIVISION
EMERSON ELECTRIC CO.
9797 REAVIS RD., ST. LOUIS, MO. 63123
(314) 577-1300, FAX (314) 577-1517
9999 HWY. 48, MARKHAM, ONT. L3P 3J3
(905) 475-4653, FAX (905) 475-4625
TYPE 1050
INDOOR - OUTDOOR
HOT WATER TEMPERATURE CONTROL
With Adjustable Reset Ratio
INSTALLATION INSTRUCTIONS
To prevent electrical shock and/or equipment
damage, disconnect electric power to system at
main fuse or circuit breaker box until installation
is complete.
Do not use on circuits exceeding specified volt-
ages. Higher voltages will damage control and
could cause shock or fire hazard.
THERMAL DATA
Range: Outdoor Temp.- -20° to 70°F (-24° to 21°C)
Boiler Temp.- 60° to 120°F (16° to 49°C) min. setting
-100° to 250°F (38° to 121°C) max. setting
Differential: - 10°F Fixed (5.5°C)
Capillary Length: Outside - 30 Ft. (9 m)
Inside -
Bulb Size:
Outside - 3/8" x 3-5/8"
Inside - 7/16" x 3" for 1/2" NPT well
Printed in U.S.A.
DESCRIPTION
PRECAUTIONS
CAUTION
WARNING
SPECIFICATIONS
15 Ft. (4.5 m)
PART NO. 37-1640C
Replaces 37-1640B
0635

Publicité

Table des Matières
loading

Sommaire des Matières pour White-Rodgers 1050

  • Page 1 BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE. DESCRIPTION The Type 1050 Indoor-Outdoor Control is designed for use on conventional hot water heating systems where it is desired to vary boiler temperature according to outdoor weather condi- tions.
  • Page 2 INSTALLATION Both the outdoor bulb and inside bulb should be installed NOTE before the control case, since capillary lengths of these bulbs will Use care not to bend or dent either of the sensing bulbs normally determine the final location for the control case. ROOF A.
  • Page 3 WIRING & OPERATION CONT. All wiring should be done in accordance with local and national electrical codes and ordinances. BURNER CONNECTIONS Burner Operation Using diaphragm INDOOR Gas Valve DIAPHRAGM The indoor-outdoor control cycles the burner OUTDOOR GAS VALVE CONTROL to vary boiler temperature to outdoor weather conditions.
  • Page 4 DIAL SETTINGS When using this control as an exact replacement, use same dial settings as for old control. A. SETTING THE ROUND DIAL: Set the round dial for “N” initially. This will enable minor additional adjustments to be made later if the specific instal- lation should require it (refer to “C”.) B.
  • Page 5: Additional Information

    DIAL SETTINGS CONT. D. ADDITIONAL INFORMATION: Charts 1, 2, and 3 show the effect which dial settings have upon boiler water temperature under varying outside air (116) 240 temperatures. Some examples of how these charts may be used are as follows: (104) 220 Example 1 (See Chart 1) –...
  • Page 6 THIS PAGE LEFT BLANK...
  • Page 7: Spécifications

    D’INSTALLER ET D’UTILISER LA COMMANDE, VOUS RISQUEZ DE CAUSER DES BLESSURES ET DES DOMMAGES MATÉRIELS. DESCRIPTION Les régulateurs intérieurs-extérieurs 1050 sont conçus pour faire varier la température de la chaudière des systèmes conventionnels de chauffage à eau chaude en fonction de la température extérieure.
  • Page 8: Installation Du Capteur Extérieur

    INSTALLATION Les capteurs intérieur et extérieur doivent tous les deux être NOTE installés avant le boîtier de commande, puisque c’est la longueur des tubes capillaires qui déterminera généralement Prendre soin de ne pas plier ou bosseler les capteurs. l’emplacement du boîtier. Toit ROOF A.
  • Page 9: Raccordements Au Brûleur

    CÂBLAGE ET MODE D’EMPLOI (suite) RACCORDEMENTS AU BRÛLEUR Utilisation avec un Fonctionnement du brûleur robinet à gaz à membrane Le régulateur intérieur-extérieur commande le brûleur afin de de faire varier la température RÉGULATEUR ROBINET À GAZ INTÉRIEUR- de la chaudière en fonction des conditions À...
  • Page 10: Réglage Des Points De Consigne

    RÉGLAGE DES POINTS DE CONSIGNE Si le régulateur est utilisé comme remplacement exact d’une autre commande, régler les points de consigne au même réglage que sur l’ancienne commande. A. RÉGLAGE DU CARDRAN ROND : Tourner d’abord le cadran rond à la position N. Ceci permettra de procéder plus tard à...
  • Page 11: Réglage Des Points De Consigne (Suite)

    RÉGLAGE DES POINTS DE CONSIGNE (suite) RENSEIGNEMENTS SUPPLÉMENTAIRES : Les graphiques 1, 2 et 3 illustrent l’effet des points de consigne des cadrans sur la température de l’eau. Voici (116) 240 quelques façons d’utiliser ces graphiques : Exemple 1 (graphique 1) : Pour déterminer la température de (104) 220 l’eau dans la chaudière lorsque la température à...
  • Page 12 THIS PAGE LEFT BLANK...

Table des Matières