5. Specifications
Models
T-out Input Isolation
T-in AC Output Voltage (V)
T-in AC Output Amps
T-in Output No. Of Phases
T-in Output Connections
T-in AC Output Configuration
T-in Connection Type
T-in Output Breaker Rating
T-out AC Output Amps
T-out output No. Of Phases
T-Out Output Connections
T-out AC Output Configuration
T-out Connection Type
T-in Output Breaker Rating
Operation
Over-Temperature
Warning LED Light (Red)
Over-Temperature
Protection Reset Device
Insulation Class
Temperature Rise
T-in Efficiency @ Full Load
T-in Efficiency @ Half Load
T-out Efficiency @ Full Load
T-out Efficiency @ Half Load
S3MT-30KWR480V
208V
113A
3PH
4-Wire (L1, L2, L3 +N + PE)
Wye
Copper Bar
125A
36A
3PH
4-Wire (L1, L2, L3 + N + PE)
Wye
Copper Bar
125A
Turns ON at 160°C±5°C (155°C/311°F to 165°C/329°F) and
turns OFF at 125°C ±5°C (120°C/248°F to 130°C/266°F)
T-in: Input Transfomer
• Transfomer output/ secondary will be OFF (Breaker opens) at 160°C ±5°C
(155°C/311°F to 165°C/329°F).
• You may turn ON (close) output breaker manually when the LED Light turns OFF.
• The warning Light will turn off at 125°C ±5°C (120°C/248°F to 130°C/ 266°F),
at which time you may close the breaker manually to re-start operations.
T-out: Output Transformer
• Transformer input/primary will be OFF (Breaker opens) at temperatures of
160°C ±5°C (155°C/311°F to 165°C/329°F).
• You may turn ON (close) input breaker manually when the LED light turns OFF.
• The Warning LED Light will turn off at 125°C ±5°C (120°C/248°F to 130°C/
266°F), at which time you may close the breaker manually to re-start
operations.
95.20%
97.50%
95.20%
97.50%
17
S3MT-60KWR480V
208V
225A
3PH
Wye
Copper Bar
250A
72A
3PH
Wye
Copper Bar
250A
180°C
125°C
96.50%
97.50%
96.5%
97.50%