3. Installation

3.8.2 S3MT-60KWR480V Connections for 50kVA or 60kVA UPS Systems

Note: This transformer is not compatible with SUT40K and SUT60K UPS models.
WARNING:
The input transformer (T-in) output neutral is not bonded to chassis ground. Please provide a means
to connect the transformer chassis ground to the transformer output neutral.
Note: The transformer chassis ground must be connected to earth ground.
IMPORTANT: You may view and/or download this manual from the tripplite.com website to view the
cable connections in colors.
Figure 3-9: UPS
Transformer Cabinet
Note: Transformer input is Delta 3-Wire (3Ph + Ground)
and output transformer is Wye 4-Wire (3Ph + N + Ground).