TRADELINE
The T834C Heating-Cooling Thermostats provide 24
to 30 Vac control in heating-cooling systems. An spdt
mercury switch makes R to W on a temperature fall for
heating, and R to Y on a temperature rise for cooling.
Integral switches control HEAT-OFF-COOL system op-
eration and AUTO-ON fan operation. See Fig. 1. Models
available for gas or oil heat/ conventional cooling systems
with common or separate R terminals and for single-stage
heat pump systems.
Fig. 1—Internal view of T834C.
FAN
SWITCH
1
1
FAN SWITCH AVAILABLE ON T834C ONLY.
M3375
This control contains mercury in a sealed tube. Do not
place control in the trash at the end of its useful life.
If this control is replacing a control that contains mercury
in a sealed tube, do not place your old control in the trash.
Contact your local waste management authority for
instructions regarding recycling and the proper disposal of
this control, or of an old control containing mercury in a
sealed tube.
If you have questions, call Honeywell at 1-800-468-1502.
WHEN INSTALLING THIS PRODUCT...
1. Read these instructions carefully. Failure to fol-
low them could damage the product or cause a hazardous
condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for your
application.
Heating-Cooling Thermostats
Application
MOUNTING HOLE
(THERMOSTAT
TO WALL OR
OUTLET BOX)
BIMETAL ELEMENT
BEHIND SCALE
ADJUSTABLE HEAT
ANTICIPATOR
INDICATOR
SYSTEM
SWITCH
MOUNTING HOLE
TEMPERATURE
SETTING LEVER
M8676
Recycling Notice
Installation
J. H. • Rev. 3-93 •
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
CAUTION
Disconnect power supply before beginning in-
stallation to prevent electrical shock or equip-
ment damage.
LOCATION
Locate the thermostat about 5 ft [1.5 m] above the floor
in an area with good air circulation at average temperature.
Do not mount the thermostat where it can be affected by:
— drafts or dead spots behind doors or in corners.
— hot or cold air from ducts.
— radiant heat from the sun, fireplaces, or appliances,
— concealed pipes and chimneys.
— unheated (uncooled) areas such as an outside wall
behind the thermostat.
MOUNTING AND WIRING
Disconnect power supply before beginning installation
to prevent electrical shock or equipment damage.
All wiring must comply with local codes and ordinances.
The T834C can be mounted directly on a wall or
vertical outlet box. Use the 193121A Mounting Plate As-
sembly (order separately) to mount on horizontal outlet box
or cover marks left by old thermostat. If mounting plate
assembly is used, review instructions provided with assem-
bly before wiring and mounting thermostat.
To wire and mount thermostat:
1. In replacement applications, check the existing ther-
mostat wires for cracked or frayed insulation. Replace any
wires in poor condition. If the wire is plastered into the
wall, make a hole next to the wires and loosen the wires so
they can be pushed back into the wall later.
2. In new installations, run wiring (if necessary) to the
thermostat location.
3. Connect the wires to the terminals on the back of the
thermostat. See Figs. 2-4 for internal schematic and typical
hookup diagrams.
4. Remove thermostat cover by pulling outward on
bottom edge of cover until it snaps free of the thermostat
base. Carefully remove and discard the foam plastic ship-
ping insert that protects the switch and bimetal assembly
during shipping.
5. Set the adjustable heat anticipator indicator to
match the current draw of the primary heating control (see
Heat Anticipator Setting).
6. Push excess wire back through the hole and plug
any opening with insulation to prevent drafts that may
affect thermostat performance.
• ©Honeywell Inc. 1993 • Form Number 69-0505B—3
M3375
T834C

Publicité

loading

Sommaire des Matières pour Honeywell Tradeline T834C

  • Page 1 4. Remove thermostat cover by pulling outward on If you have questions, call Honeywell at 1-800-468-1502. bottom edge of cover until it snaps free of the thermostat base. Carefully remove and discard the foam plastic ship-...
  • Page 2 Fig. 2—Internal schematic and typical hookup diagram for single-transformer heating-cooling systems. (HOT) SWITCH FAN RELAY TEMP. FALL AUTO COOL RELAY ANTICIPATOR ANTICIPATOR SYSTEM SWITCH COOL HEAT HEAT COOL HEAT RELAY POWER SUPPLY. PROVIDE DISCONNECT MEANS AND (HOT) OVERLOAD PROTECTION AS REQUIRED. IN SINGLE TRANSFORMER SYSTEMS, JUMP RC AND RH.
  • Page 3 Fig. 4—Internal schematic and typical hookup diagram for systems with separate heating and cooling transformers. (HOT) SWITCH FAN RELAY TEMP. FALL AUTO COMPRESSOR CONTACTOR ANTICIPATOR ANTICIPATOR SYSTEM SWITCH (HOT) COOL HEAT HEAT COOL HEAT RELAY POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
  • Page 4 AUTO. In gas- or oil-fired systems, fan opera- M2044 tion is controlled by the thermostat in cooling and by the Automation and Control Solutions Honeywell International Inc. Honeywell Limited—Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley, MN 55422 Scarborough, Ontario M1V 4Z9 www.honeywell.com/yourhome...
  • Page 5 Pour obtenir de plus amples renseignements, téléphonez 4. Retirer le couvercle du thermostat en le tirant par le bas sans frais à Honeywell en composant le 1-800-468-1502. jusqu’à ce qu’il se dégage du support du thermostat. Retirer avec soin l’emballage plastique à bulles. Cet emballage Installation protège l’interrupteur et la bilame pendant l’expédition.
  • Page 6 Fig. 2—Schéma interne et raccordement type du T834C pour les systèmes de chauffauge et de refroidissement standard à un transformateur. L1 (SOUS TENSION) COMMUTATEUR DU VENTILATEUR RELAIS DU CHUTE DE VENTILATEUR TEMPÉRATURE AUTO CONTACTEUR DU COMPRESSEUR H1 RÉSISTANCE C1 RÉSISTANCE ANTICIPATRICE ANTICIPATRICE COM-...
  • Page 7 Fig. 4—Schéma interne et raccordement type du T834C muni de transformateurs distincts pour le chauffage et le refroidissement. L1 (SOUS TENSION) COMMUTATEUR DU VENTILATEUR RELAIS DU VENTILATEUR CHUTE DE TEMPÉRATURE AUTO CONTACTEUR DU COMPRESSEUR H1 RÉSISTANCE C1 RÉSISTANCE ANTICIPATRICE ANTICIPATRICE COMMUTATEUR DU SYSTÈME L1 (SOUS...
  • Page 8 6 °C (10 °F) au-dessus de la température ambiante. Le système de refroidissement et le ventilateur devraient s’arrêter. Solutions de régulation et díautomatisation Honeywell International Inc. Honeywell Limited—Honeywell Limitée 1985 Douglas Drive North 35, Dynamic Drive Golden Valley, MN 55422 Scarborough (Ontario) M1V 4Z9 www.honeywell.com/yourhome...