Menu
Installer setup Operation setup
6.1
Heat
To set various water &
ambient temperatures for
heating�
Default Setting
Setting Options / Display
Water temp� for heating ON /
Outdoor temp� for heating OFF /
T for heating ON /
Outdoor temp� for heater ON
Water temp. for heating ON
Heating ON
Compensation
temperatures in
curve
compensation curve or
direct input�
Water temp. for heating ON Compensation curve
Input the 4 temperature
X axis: -5 °C, 15 °C
points
Y axis: 55 °C, 35 °C
(2 on horizontal X axis,
2 on vertical Y axis)�
• Temperature range: X axis: -15 °C ~ 15 °C, Y axis: See below
• Temperature range for the Y axis input depends on the model:
1� WH-SDC model : 20°C ~ 55°C
2� WH-SHF model & Back up heater is enabled: 25°C ~ 65°C
3� WH-SHF model & Back up heater is disabled: 35°C ~ 65°C
4� WH-SXC/SQC model : 20°C ~ 60°C
• If 2 zone system is selected, the 4 temperature points must also be input for Zone 2�
• "Zone 1" and "Zone 2" will not appear on the display if only 1 zone system�
Water temp. for heating ON Direct
Temperature for heating
35 °C
ON
• Min� ~ Max� range is conditional as follows:
1� WH-SDC model : 20°C ~ 55°C
2� WH-SHF model & Back up heater is enabled: 25°C ~ 65°C
3� WH-SHF model & Back up heater is disabled: 35°C ~ 65°C
4� WH-SXC/SQC model : 20°C ~ 60°C
• If 2 zone system is selected, temperature set point must input for Zone 2�
• "Zone 1" and "Zone 2" will not appear on the display if only 1 zone system�
Outdoor temp. for heating OFF
Temperature for heating
24 °C
OFF
EN
19