Toshiba Carrier MMD-AP0076BHPUL Manuel D'installation page 19

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

<In the case of combining with outdoor units other than Super Modular Multi System u series (SMMS-u)>
Control wiring between indoor units, and outdoor unit (L2, L3)
(2-core shield wire, non-polarity)
Central control line wiring (L1)
(2-core shield wire, non-polarity)
Control wiring between outdoor units (L4)
(2-core shield wire, non-polarity)
• The length of the communication line (L1+L2+L3) means the total length of the inter-unit wire length between
indoor and outdoor units added with the central control system wire length.
Central control device
<Other than U series>
Outdoor unit
(SMMS-i)
(SMMS-e)
(MiNi SMMS)
etc.
<U series>*
Indoor unit
<U series>*
Remote controller
* Even if the indoor unit and the remote controller are "other than U series", the wiring specification are
the same.
35-EN
1116950170_01_EN.indd 18
1116950170_01_EN.indd 18
AWG16
(Up to 3280'10" (1000 m))
Wire size :
AWG14
(Up to 6561'8" (2000 m))
Wire size :
AWG14
(Up to 328'1" (100 m))
[Communication line]
(L1+L2+L3) = Up to 6561'8" (2000 m)
Remote controller wiring
2-core with non-polarity wire is used for wiring of the remote controller wiring and group remote controllers wiring.
Remote controller wiring, remote controller inter-unit
wiring
Total wire length of remote controller wiring and remote
controller inter-unit wiring = L + L1 + L2 + ... Ln
T
t o
l a
i w
e r
e l
n
g
h t
f o
e r
m
o
e t
c
o
t n
o r
e l l
i r
t n
r e
u -
n
t i
w
CAUTION
The remote controller wire (Communication line) and AC 208/230V wires cannot be parallel to contact
each other and cannot be stored in the same conduits. If doing so, a trouble may be caused on the
control system due to noise or other factor.
communication specifications when carrying out the installation, maintenance, or repair For its details, refer to
8 Electrical connection.
Indoor unit
Indoor unit
L
Remote
controller
L1
wiring
Remote
Remote controller inter-unit wiring
controller
– 18 –
Wire size: AWG20 to AWG14
In case of wired type only
Up to 1640'5" (500 m)
In case of wireless type
Up to 1312'4" (400 m)
included
r i
n i
g
=
L
1
+
L
2
+
...
L
n
Up to 656'2" (200 m)
Indoor unit
Indoor unit
L
2
L
n
EN
FR
ES
36-EN
10/21/20 12:31 PM
10/21/20 12:31 PM

Publicité

Table des Matières
loading

Table des Matières