0
TRI
SYS sarl –
300 Rue des Arts et Métiers, 21410 PONT DE PANY
2
6.5 Radio function test (slave)
This RLT function (Radio Link Test, EEP §A5-3F-00
(master), to perform a radio test range (slave):
a) On the diagnostic product, activate the master RLT mode (refer to its manual instruction)
b) On this receiver, activate the slave RLT mode by a short press (approximately 0,5s) on LRN and
CLR simultaneously. This mode is confirmed by the regular flashing (orange) of the 4 LEDs.
c) To exit this function, short press (approximately 0,5s) on the LRN button. the output is confirmed by
the stopping of regular flashing of the 4 LEDs. In the absence of test activity, this function stops
automatically after 30 seconds.
6.6 Repeater 2 levels function
The repeater function of the 4 channels receiver is used to increase the range between
transmitters and receivers. When the radio signal from a transmitter is received, it is retransmitted to the
associated receiver via a maximum of two repeaters. Radio signals are received and transmitted
automatically.
a) On the receiver, activate the slave RTL mode by a short press (approximately 0,5s) on LRN and
CLR simultaneously. This mode is confirmed by the regular flashing (orange) of the 4 LEDs; then
short press (approximately 0,5s) CLR. This mode is confirmed by the red LED 1 flashing.
b) The current configuration is displayed by the number of LED 1 flashing:
1 - repeater off
2 - activated repeater, level 1
c) To change the mode of operation of the repeater, short press CLR the number of times
corresponding to the desired mode (b). Each press is acknowledged by maintaining LED 1 on for
the time of the press. The new configuration is stored and enabled, after 1,5s without any press. As
soon as the flashing restarts, the new configuration is displayed and editable again (back to b).
d) To exit this function, short press (approximately 0.5s) on the LRN button. The output is confirmed
by stopping the flashing of LED 1. In the absence of activity, this function stops automatically after
30 seconds.
Note:
- This function is disabled on delivery of the receiver.
6.7 Factory configuration
With this function, the receiver can be reset to the factory configuration as it was when the product was
delivered:
a) Switch off the device.
b) Hold down the CLR button, then switch on the device,
c) Once the LED 1 is orange, wait for LED 1 to turn red (5s) then release the CLR button.
d) Press the CLR button again for about 1s, the red LED 1 goes out.
e) The product is in factory configuration.
Note:
- In the delivery state of the receiver, no transmitter is programmed, the repeater is disactivated and the
consumption data is zero.
7. Troubleshooting
7.1 New or existing installation
• Check the circuit breaker, the electrical supply and the load connected to the receiver associated with
this sensor (qualified electricians).
• Check the connected load and the connecting cables (qualified electricians).
• If the receiver functions at a shorter distance relative to the sensor, it is subject to interference or used
outside the transmission range.
• Search the system environment for changes that could cause the interference (for example movement
of metallic cabinets, furniture or partitions).
• Use the sensor or receiver in a more suitable location.
• Clear the receiver and perform a new learn process.
7.2 Automatic activation of the receiver
• The cause may be the activation of a sensor external to the system which has by chance been
programmed on the receiver.
• Clear the receiver and perform a new learn process.
7.3 Limitation of the range of the radio signals
• Transmitter/receiver used close to metallic objects or close to materials containing metallic elements.
Observe a distance of at least 10 cm.
• Humidity in the materials.
• Device emitting high frequency signals such as: audio and video systems, computers, electronic
ballasts or fluorescent tubes. Observe a distance of at least 0.5 m.
7.4 Contacts
E-mail: ............................
contact@trio2sys.fr
8. Recycling of the device
In accordance with European Directive 2012/19 / EU on waste electrical and electronic
equipment and its implementation in accordance with national laws, this logo means that
devices must not be thrown away with household waste. The hazardous substances they
are likely to contain can harm health and the environment. Have these devices taken
back by your distributor or use the selective collection means made available by your
municipality.
9. Declaration of conformity
This product can be marketed and distributed in the countries of the European Union. Hereby TRI0
declares that radio equipment 10020110 is in compliance with directive 2014/53/EU, known as the RED
Directive.
The full text of the EU declaration of conformity is available at the following internet address:
www.trio2sys.fr
.
1
For more details, see Communication Profiles – EEP available at:
www.enocean-alliance.org/what-is-enocean/specifications/
TOC2001NUcc_0421
1
) master slave allows, through a diagnostic product
Receiver
3 - activated repeater, levels 2
D. Girard
0
LINE
2
SYS
2
6/6