1. General
1.1 Use
The modular 4 channels switch receiver
used to receive radio signals from switch transmitters or
sensors (see compatibility table §6.1). Designed for switching
LED and compact fluorescent lighting loads, it can also switch
resistive loads (halogen), fluorescent tubes, TBT halogen lamps
with ferromagnetic and electronic transformer, power contactors
or small motors.
The 4 channels switch receiver is equipped with the « repeater »
function as well as the « consumption indicator » function (see
§6.6 and §6.3).
Before use, the transmitters must be assigned to a receiver. Each
sensor or transmitter can control an unlimited number of
receivers.
Note: Read the user manual carefully before commissioning. To
consult the consumption indications, it is recommended to
connect the 4 channels switch receiver 10020110 with a suitable
software.
1.2 Guarantee terms
This operating manual is an integral part of the device and our guarantee terms. It must always be
delivered to the user. We reserve the right to modify the technical design of these devices without warning.
0
TRI
SYS products are manufactured and their quality checked by making use of the latest technologies
2
and taking into account the applicable national and international directives. If nevertheless a fault arises,
0
TRI
SYS undertakes to remedy the default as follows, without prejudicing the rights of the end customer
2
that arise from the sales contract with his reseller:
If the event of exercising of a legitimate and regular right, TRI
the device fault or supply a fault-free device. Any claim beyond this and all claims for consequential
damages are excluded.
A legitimate fault exists if the device cannot be used at the time of delivery to the end customer because
of a design or manufacturing defect or if its practical use is severely limited. The guarantee is void in
cases of natural wear and tear, incorrect use, incorrect connection, where the device has been repaired
or external influence. The guarantee period is 24 months (from the date of invoicing). French law applies
to the regulation of guarantee rights.
2. Safety
WARNING! Risk of electric shocks! (See UTE C18-150) The device contains live internal
WARN
components. Risk of wounds or injuries if contact occurs! All work on the mains supply
network and the device must only be carried out by authorised professional technicians.
• Before carrying out any work, switch-off and isolate the device.
• Before c
• Secure the device to prevent it being switched back on.
• Check the device is in a zero-volts state.
• Carefully reclose the casing before reconnecting to mains power.
Observe the following points:
• The laws, standards and directives in force.
• The device operating manual and best practice at the time of installation.
• An operating manual can only give general instructions. They must be interpreted in the context of a
specific installation.
The device is intended solely for use conforming to its purpose. Any repairs or modifications by the user
are forbidden! Do not use with other devices the operation of which could endanger people, animals or
property.
3. Technical characteristics
General characteristics
Transmission frequency band
Transmit power
Power supply
Terminal capacity
-2-
Output
4 contacts micro distance (µ) opening
contacts, I
=100mA
min
Receiver EEP profile
Receiver category
Power measurement accuracy
Number of modules
Mounting type
Consumed power
Ambient temperature
Storage temperature
Ambient humidity
Degree of protection
Installation altitude
-1-
The output voltage of the 4 channels receiver is the same as the supply voltage.
-2-
Consult us for other types of charges.
-3-
For powers greater than 10W.
-4-
Power consumed without activation of the relays.
Range in buildings
Masonry
20m, through 3 walls at most
Reinforced concrete
10m, through 1 wall/ceiling at most
Plasterboard / wood
30m, through 5 walls at most
Note: The signal strength between the transmitter and the receiver decreases as the distance increases.
Where there is a line of sight connection, the range is approximately 30m in corridors and 100 m in large
workshops or halls. The range can be increased with an
Respect a minimum range of 10 cm between transmitter and receiver.
TOC2001NUcc_0421
EN
0
LINE 10020110 is
2
0
SYS, may at its sole discretion, rectify
2
From 868,0 MHz to 868,6 MHz
+10 dBm
-1-
110 - 230V
/ 50 Hz
7mm
1x1,5² à 2,5² max rigid
max µ4x1.5A/4x345VA resistive (cos φ=1)
LED: 4x130W
Compact fluorescent: 4x130W
Halogen: 4x345W
Inductive: 4x300W (cos φ= 0,4 à 0,6)
D2-01-00
2
-3-
2% +/- 1 digit
1 module of 17.5 mm
DIN rail mounting
-4-
< 0.35 W
From -10°C to +45°C
From -20°C to +80°C
From 0 to 75%hr (without condensation)
IP20 with plastron
2000m max.
0
.
LINE repeater
2
4. Installation and initial use
4.1 Safety instructions
The installation and initial use must only be performed by authorised qualified electricians. The electrical
installation must be placed off-load before connection it to the mains. Conform to the legislation and
standards in force in the country of use.
4.2 Installation
• This product is designed for indoor use. It is maintenance free.
• This product is intended for installation only on horizontal DIN rail, in an electrical panel (mounted on
0
LINE
2
a vertical wall) with compulsory installation of a plastron which will be connected to the ground of the
installation if it is metallic.
• For compliance with the standard reference, height of the plastron (compared to the above DIN rail)
must not exceed 48 mm with a minimum thickness of 1 mm.
• NEVER install the receiver in a metal casing or in the immediate vicinity of large metallic objects.
• Installation on the ground or close to the ground is not recommended. Thank you to refer to the
installation standards of each country.
• Protect the supply line with a circuit breaker 6A curve C adapted to the installation.
Connection principle diagram:
4.3 Description of the connection
- Description of the 4 channels receiver connection:
4.4 Initial use
• Connect power to the electrical installation after it has been installed.
• Program the transmitter on the receiver (see § 5).
Schematic diagram of electrical
connection to lighting loads.
They can be replaced by other
types of loads (see table §3).
4/6