DEFAULT CONFIGURATION
PARAMETERS
The configuration parameters can be loaded with
predetermined default values. These data are the
typical values loaded in the instrument prior to
shipment from factory. To load the default values
proceed as follows:
a) The internal switch (V101, see fig. 12) should
be open.
b) The upper display will show:
COnF
c) Push the t pushbutton; the display will show
the firmware version.
C0nF
A. 0 0
d) Maintaining the pressure on the t
pushbutton, push the s pushbutton also.
The instrument will show:
O F F
d F L t
e) Press s pushbutton to select between table 1
(European) or table 2 (American) default set
of parameters; the display will show:
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
t b 1
d F L t
f) Press FUNC pushbutton; the display will show:
LOAd
It means that the loading procedure has been
initiated.
After about 3 seconds the loading procedure is
terminated and the instrument reverts to
visualization as in point b).
PARA.
TABLE 1
TABLE 2
P1
3
21
P2
----.
----.
P3
0
0
P4
400
1000
P5
rEL
rEL
P6
rEV
rEV
P7
4
4
P8
H.A.
H.A.
P9
1
1
P10
4
4
P11
10
10
P12
10
10
P13
H.A
H.A.
P14
8
16
P15
8
16
P16
4
8
P17
0
0
P18
rEV
rEV
P19
OFF
OFF
P20
rEV
rEV
A. 2