fisair DIPHUSAIR-MT2 Manuel D'installation Et De Maintenance page 78

Humidificateurs isothermiques par injection de vapeur sèche
Table des Matières

Publicité

85˚
Max
Figure-11 Acceptable Mounting Orientations for Non-Steam Applications
Approx.
45°
F-27169-3
For non-steam application the globe valve assembly must be mounted so that the
actuator is at least 5° above the horizontal (Figure-11) to ensure that any condensate
that forms will not travel into the mounting bracket or actuator.
On steam applications, the globe valve assembly must be mounted approximately 45°
from horizontal.
Temperature Restrictions: For maximum ambient 140 °F (60 °C) the maximum
allowable fluid temperature should not exceed valve rating. See F-27252 Selection
Guide for specific ratings.
Figure-12 Acceptable Mounting Orientation for Steam Applications
© Copyright 2004 Invensys Building Systems, Inc. All rights reserved.
1-3/4 (45)
Minimum
Clearance
85˚
Max
Approx.
45°
11