fisair DIPHUSAIR-MT2 Manuel D'installation Et De Maintenance page 153

Humidificateurs isothermiques par injection de vapeur sèche
Table des Matières

Publicité

3.10 High temperature extension kit
The extension kit is to be used on applications above 130 °C to up to 240 °C. There are two kit options of up
to 180 °C and another for up to 240 °C
1.
Unscrew the actuator mounting plate screws
for pillars.
2.
Screw the extension pillars into actuator pillars
and tighten to 12 Nm.
3.
Screw the actuator mounting plate screws into
pillars and tighten to 25 Nm.
4.
Mount the coupling extension into the actuator
coupling until it snaps closed.
High temperature
extension kit
for up to 240 °C
38
AEL3 Electric Linear Actuators
High temperature
extension kit
for up to 180 °C
Fig. 56
IM-P344-01 CTLS Issue 7

Publicité

Table des Matières
loading

Table des Matières