5.
Make sure that the spindle is fully retracted into the actuator and handle is up so that the spring is
secured in place.
Fig. 7
6.
Place the mounting flange and actuator over the valve bonnet thread.
7.
Refit the actuator retaining nut and tighten (50 Nm for M34).
Fig. 8
IM-P344-01 CTLS Issue 7
AEL3 Electric Linear Actuators
Warning
Risk of injury due to limbs being trapped
• Avoid contact with the danger areas.
45°
45°
click
13