11 Annexe
Codage de l'octet d'état pour la valeur de sortie PA
Vous trouverez d'autres informations pour le codage de l'octet d'état dans le Device Description
3.02 sur www.profibus.com.
Code d'état
0 x 00
0 x 04
0 x 0C
0 x 10
0 x 1f
0 x 44
0 x 48
0 x 4c
0 x 51
0 x 52
0 x 80
0 x 84
0 x 89
0 x 8a
0 x 8d
0 x 8e
72
Description selon norme
Profibus
bad - non-specific
bad - configuration error
bad - sensor failure
bad - sensor failure
bad - out of service
constant
uncertain - last unstable
value
uncertain substitute set
uncertain - initial value
uncertain - sensor; conver-
sion not accurate - low
limited
uncertain - sensor; conver-
sion not accurate - high
limited
good (non-cascade) - OK
good (non-cascade) - ac-
tive block alarm
good (non-cascade) - ac-
tive advisory alarm - low
limited
good (non-cascade) - ac-
tive advisory alarm - high
limited
good (non-cascade) - ac-
tive critical alarm - low
limited
good (non-cascade) - ac-
tive critical alarm - high
limited
Cause possible
Flash-Update actif
•
Erreur de réglage
•
Erreur de configuration au PV-Scale (PV-Span too
small)
•
Unité de mesure ne convient pas
•
Erreur dans tableau de linéarisation
•
Erreur du hardware
•
Erreur du convertisseur
•
Erreur d'impulsion de fuite
•
Erreur du déclencheur d'impulsion
•
Erreur de gain de valeur de mesure
•
Erreur de mesure de la température
Mode "Out of Service" activé
Valeur de remplacement Failsafe (mode Failsafe =
"Last value" et valeur de mesure déjà valable depuis la
mise en route)
•
Mettre en route la simulation
•
Valeur de remplacement Failsafe (mode Failsafe =
"Fsafe value")
Valeur de remplacement Failsafe (mode Failsafe =
"Last valid value" et encore aucune valeur de mesure
valable depuis la mise en route)
Valeur du capteur < limite inférieure
Valeur du capteur > limite supérieure
OK
Static revision (FB, TB) changed (actif pendant 10 sec.
après avoir écrit le paramètre de la catégorie static)
Lo-Alarm
Hi-Alarm
Lo-Lo-Alarm
Hi-Hi-Alarm
VEGABAR 86 • Profibus PA