13. Technical Specifications
MODEL
CAPACITY
TOPOLOGY
INPUT
Voltage
Voltage Range (Ph-N)
Phase
Operating Frequency
Frequency Range
Power Factor
THDi
Inverter Bridge
OUTPUT
Voltage
AC Voltage Regulation
Frequency
Frequency Range
Overload
AC mode
Battery mode
Crest Factor
Harmonic Distortion
Output Waveform
BYPASS
Automatic Bypass
Manual Maintenance Bypass
Transfer Time
Default Bypass Voltage Tolerance
Overload
BATTERY
Battery Type*
Battery Capacity*
Float Voltage
Boost Voltage
End of Discharge Voltage
Battery Storage Time*
Battery Charger Capacity
ENVIRONMENT
Efficiency (Inverter Mode)
Efficiency (ECO Mode)
Operating Temperature
Storage Temperature (Excl Battery Module)
Operating Humidity
Operating Altitude
Audible Noise
Protection Degree
Color
* Applies to Small- and Medium-Frame systems with internal battery modules.
20K
40K
20kVA/18kW 40kVA/36kW
60kVA/54kW
Voltage and Frequency Independent (VFI) True on-line Double Conversion
90V to 146V (100% load) / 70V to 89V (70% load)
208/220V (3ph, 4 wire, neutral reference to bypass neutral)
<2% (100% linear load); <4% (100% non-linear load)
Maintenance-free sealed valve-regulated lead acid (VRLA)
32 to 104°F / 0 to 40°C (Output capacity will be de-rated 90% when temperature is 88~95°F / 31~35°C;
will be de-rated to 80% when temperature is 96~104°F / 36~40°C)
<3280 ft. / <1000 m (1% derating per 328 ft. / 100 m above 3280 ft. / <1000 m)
60K
80K
80kVA/72kW
100kVA/90kW
208/220V (Ph-Ph), 120/127V (Ph-N)
3-phase, neutral and ground
50/60Hz (selectable)
40Hz ~ 70Hz ± 0.1Hz
>0.99%
<3%
IGBT technology
<1% (balanced load)
50/60Hz (selectable)
40Hz ~ 70Hz ± 0.1Hz
105-110%: 60 min.
111-125%: 10 min.
126-150%: 1 min.
>150%: 200 ms
105-110%: 60 min.
111-125%: 10 min.
126-150%: 1 min.
>150%: 200 ms
3:1
Pure sine wave
Standard
Standard
0 ms
+15/-20%
105 to 110%: 60 min.
111 to 125%: 10 min.
126 to 150%: 1 min.
>150%: 200 ms
18Ah (per battery module)
2.3V/cell
2.35V/cell
1.67V/cell
6 months (without recharge, 77°F / 25°C)
8A (per power module)
>92%
>98%
5 to 140°F / -15 to 60°C
0 to 95% (non-condensing)
<75dBA
IP20
RAL 9005 (Black)
35
100K
120K
120kVA/108kW 140kVA/126kW
140K