Battery Back-Up Power Supply
Installation Diagram
Note: The StormPro backup system and existing
primary pump must be plugged into separate
dedicated outlets
WALL OUTLET
W/SEPARATE
WALL OUTLET
CIRCUIT FOR
W/SEPARATE
PRIMARY PUMP
CIRCUIT FOR
BACK-UP SYSTEM
STORMPRO
5 AMP
POWER SUPPLY
STORMPRO
BACK-UP
SWITCH
INSTALLING THE BACKUP PUMP:
Sump pump ON level must be lower than the back-
up pump ON level. Set the backup pump switch
higher than the primary switch.
1. Place the pump into the pit. Secure the dis-
charge piping and attach the switch to the pipe.
Make sure the switch ON level is at least 4
inches below the top of your pit and it is set
at a level higher than the primary switch's ON
level. Once in place, tighten the switch clamp
securely to the pipe.
2. Once the switch is set in place and the di
charge piping is properly installed, you can
piggy back plug the pump and the switch into
the receptacle located on the StormPro power
supply. Then plug the power supply into the
wall outlet.
Register your product at
www.sumpro.com
OPERATION MANUAL
Dated: 12/12/08
Supersedes: None
Document No.: SP-OM
3. Test run your system on AC power by activating
4. If battery voltage falls below a usable charge,
5. Battery voltage may recover and allow brief pe-
BASIN
PRIMARY
To test the Unit simply unplug it from the receptacle
SUMP PUMP
add water to sump until pump pumps sump down.
Only run the Pump supplied with the Battery Back-
STORMPRO PUMP
Up System for a few cycles. You can repeat
this if you wish but it is not necessary. If the Unit
works the first time it is sure to work time and time
again. Be sure that you remember to plug the Unit
back into the receptacle after you have completed
the test. NOTE: If while testing the Unit the Pump
does not turn on, the following steps should be
taken:
1. Check the charger and inverter lights to see if
2. Check the circuit breaker.
3. Plug the Pump you have plugged into the Unit
4. Check sump water level to see that Pump is bei
the switch, then unplug the power supply from
the electrical outlet and test the pump on DC
power by activating the switch. Be sure to plug
the power unit plug back into the wall outlet.
PUMP WILLSTOP:
Power loss (inverter on) light OFF
Battey charging light FLASH
Fully charged light OFF
riods of Operation.
Testing
they are on.
directly into a live building receptacle. If the
Pump runs, recheck all the battery connections,
and battery voltage.
required to run.