ATTENTION: Before starting the electrical connections, check the voltage (230V or 400V) selector switch to be
set correctly.
!
In cases a motor with mechanical brake is used or a control board ELPRO 14 is replaced, the DIP-switch A
No.12 has to be in OFF.
Dip-Switch A
1 = ON Photocells stop gate in opening
2 = ON Radio, no reversing in opening
3 = ON Automatic closing
4 = ON Pre-flashing enabled
5 = ON Radio step-by-step
6 = ON Dead man
Dip-Switch B
1 = ON set braking duration
2 = ON set additional stop time after braking when safety devices are activated
3 = ON set electric lock or courtesy lamp duration
4 = OFF Blank
Accessory
Photocells in
Opening:
IN I
F A D
Key-switch:
F A
D I
N I
F A
D I
N I
Radio Contact
(step by step mode):
2
4
3
5
7
6
8
A
9
S
T O
P
B
F A
D I
N I
Indication lamp
output
24V- max 3W:
Limit switch:
page 10
SINGLE – THREE PHASE ELECTRONIC CONTROL BOARD WITH ELECTRONIC BRAKE FOR
DOUBLE-LEAF SLIDING GATE AUTOMATIC SYSTEMS WITH OR WITHOUT LIMIT SWITCHES
7 = ON Flasher off in Dwell time in Automatic
8 = ON Gate re-closing in Opening and Dwell on Photocells engaging
9 = ON DSA control of photocells before any movement
10 = ON Photocells not obstructed before moving
11 = Blank
12 = ON Electronic brake enabled
Electrical connections
1 2
All NC contacts of safety
accessories such as
NC
Photocells (receivers)
must be connected in
NC
series with terminals
1 and 2
NO and NC contacts to be connected
3 4 5 6
to the respective terminals in the key-
or button-switches.
All of the possible setting combinations
are described in the instructions sheets
NC
included with the respective control
accessories
Any NO connection to these two terminals
will perform the following:
3
7
- Opening only: Dip 2=ON and Dip 5=OFF
- Gate travel reversing by any pulse
Dip 2=OFF and Dip 5=OFF
- Step by step: Open-Stop-Close-Stop
Dip 2=OFF and Dip 5=ON
- No new pulse is accepted in opening. In
Dwell phase and in closing any new pulse
stops and reverses gate travel:
Dip 2=ON and Dip 5=ON
Output for a 24V max 3W indication lamp
3
11
showing the status of the system:
Lamp On = Gate open
Lamp Off = Gate closed
0.5s (fast) flashing = gate closing
1s (normal) flashing = gate opening
IMPORTANT: if no limit switches
are involved, link out limit switches terminals.
Limit switches ( L-sw.) must have normally closed contacts.
LIMIT SWITCH
8 9 10
MOTOR 1
= Limit switch Closing
L-sw.C.
= Limit switch Opening
L-sw.O.
12 13
24Vac output max. load:
n°1 radio receiver
n°3 pairs photocells
LIMIT SWITCH
MOTOR 2
30 31
32
DIP-SWITCH - A
ON
OFF
1 2 3 4 5 6 7 8 9 10 11 12
DIP-SWITCH - B
ON
OFF
1 2 3 4
Dip-Switch setting and LED indication of functions
DIP-SWITCH-A N° 1:
ON: stop gate/s in opening and reverse
travel in closing when cleared
OFF: no stop in opening and reverse travel in
1
closing when obstructed
L1 ON = no obstacle, it goes off
in case of obstruction
L4 OFF = no OPENING contact, it goes on
whenever an opening pulse is given
L5 OFF = no CLOSING contact, it goes on
whenever a closing pulse is given
L6 ON = STOP contact closed, it goes
off whenever a stop pulse is given
DIP-SWITCH-A N°2 and N°5:
ON: It does not stop and reverse gate travel
in opening
OFF: always stops & reverses in opening
2
ON: step by step with intermediate stop
OFF: gate travel reversed by any radio pulse
5
L7 OFF = no RADIO contact, it goes on by
any radio pulse
L8 ON = OFF on engaging L.sw. Closing M1
L10 ON = OFF on engaging L.sw. Opening M1
L30 ON = OFF on engaging L.sw. Opening M2
L31 ON = OFF on engaging L.sw. Closing M2