Service
Status on DI1 input
Status on DI2 input
Read temperature at sensor "Sc3"
Read temperature at sensor "Sc4"
Status on DI3 input
Status on DI4 input
Status on DI5 input
The controller can give the following messages
E1
Error
Fault in controller
message
E2
Regulation is outside the range, or the control
signal is defective *
A2
Alarm
Low P0
message
A11
Refrigerant not selected
A17
High Pc
A19
Compressor 1 error
A20
Compressor 2 error
A21
Compressor 3 error
A22
Compressor 4 error
A23
Compressor 5 error
A24
Compressor 6 error
A25
Compressor 7 error
A26
Compressor 8 error
A27
Room temperature alarm (Saux1 temp.)
A28
DI 1 alarm. Terminal 46 interrupted
A29
DI 2 alarm. Terminal 47 interrupted
A30
DI 3 alarm. Terminal 49 interrupted
A31
DI 4 alarm. Terminal 50 interrupted
A32
DI 5 alarm. Terminal 52 interrupted
A34
Fan alarm. There is no signal on DI1 input
A45
Regulation stopped
S0
Status
Regulation
message
S2
Wait for "c01"
S5
Wait for "c07"
S8
Wait for "c11" or "c12"
S9
Wait for "c14" or "c15"
S10
Refrigeration stopped by the internal or external
start/stop function
S25
Manual control of outputs
S34
Safety cutout. Setting A30 is exceeded or all
safety inputs (29-36) are open
PS
Info
Access code is required before you have access to
the settings
* At water cooler management without frost protection may alarm from a not
mounted P0 input suppressed by connecting the signal from the PC (terminal 61) to
P0 (terminal 58).
AK-PC 530
u10
u37
u44
u45
u87
u88
u89
The actual compressors
safety circuit is
interrupted.
That is to say the signal
is missing on one of the
terminals 29-36
Instructions RI8LZ452 © Danfoss 05/2010
Messages can be brought up on the display by briefly pressing
the uppermost key. If there is more than one alarm, they can be
scrolled through
Factory setting
If you need to return to the factory-set values, it can be done in
this way:
- Cut out the supply voltage to the controller
- Keep the middle button pressed at the same time as you recon-
nect the supply voltage
°C
°C