5.4
Connecting the hose lines
See chapter "Application example" for an example of how to route the hoses
from the product to the tank.
Verify that the hoses are resistant to the stored liquid and its vapours.
1. Use oil- and water-resistant plastic hoses 6 x 2 mm for the measuring line
(red), the suction line (transparent) and the pressure line (transparent).
2. In outdoor or underground applications, install the hoses in suitable liquid-
tight, shock-resistant and weather-resistant protective pipes.
3. The hose lines must have the full cross section over the entire length;
there must be no bends and indentations.
4. Do not install any shut-off fittings.
Mounting
2. Plug the EnOcean® wire-
less module into the slot.
When plugging in the
wireless module, ensure
the following:
- The position of the
antenna must be at the
right side (close to the
housing wall).
- All pins must be inserted
into the female connec-
tor.
3. Push the antenna of the
EnOcean® wireless mod-
ule into the two housing
openings of the product.
4. Close the cover of the
product.
Europress
EN
28