EN
Elements
B1
L1
B1
L1
L1
Activation from sleep
B2 B4 B6
L2
B3 B4 B6
Set temperature Touch B3.
L3
B4 B6
Change value of se-
L4-L7
B4 B5 B6
L2
Switch on/off the inten-
sive ventilation (boost)
B4 B6
L4-L7
Review and cancel
L2-L7
B2 B3 B5
"Child safety feature"
Connection
Flashing „Con" – connecting.
Shining „noC" – connection lost.
Fan
speed
cont
• Selecting 4 preset speeds
• Selecting percentage value of speed (0, 20-100%)
• User menu speeds are set in intervals of 5%
• Service menu speeds are set in intervals of 1%
• Selecting 4 preset pressure values by using pressure sensor
• Maximum speed is limited by timer which can be easily set when maximum fan speed is activated (boost)
• Maximum speed can be activated using fast button. When preset maximum fan speed (boost) time is over,
previous speed is automatically restored.
• 0..10 VDC CO2 sensor can be connected for activation of maximum speed based on the given CO2 param-
eters
Temperature
Te
• In controller, desired temperature can be set between 15 and 35°C
• Supply air and set temperatures can be displayed interchangeably (set temperature is displayed for 5 sec-
onds, then supply air temperature is displayed for 2 seconds)
Remote
control
Controller supports fully confi gurable Modbus interface. Panel can operate as master and slave device in
modbus network and also it can be fully controlled and confi gured not only via service menu but also via mod-
bus interface.
www.salda.lt
Coomand Action
Switch on Press down for 2 seconds
B1
Switch off Press down for 2 seconds
B1
Press any button.
mode
Set fan speed Touch B2.
Increase by touching B4,
lected setting
decrease by touching B6
2 sekundes palaikyti B5.
For canceling, press down
alarms
B2 and B3 for 3 seconds.
CO2 blow off
On/off
Press down B3, B2 and
B5 for 2 seconds.
ind
ndication
n
ntrol
co
control
ol
(Modb
dbus)
Indication
L1 lights on.
L1 lights off.
L1 fl ashes slowly in sleep mode.
L2 lights on. Speed is adjusted by touch-
ing elements B4 and B6
L3 lights on. Temperature is adjusted by
touching elements B4 and B6
Numbers change in the segment display.
L4, L5, L6, L7 shows selected fan speed.
L2 fl ashes. Remaining time in seconds is
shown in the segment display (for values
above 600s, time is shown in minutes).
Time is adjusted by touching B4 and B6.
Maximum BOOST running time: 180m.
(3h)
In case of alarms, L4, L5, L6, L7 fl ash
and alarm code is shown in the segment
display (A.01, A.02 etc.). You can review
alarm list by using elements B4 and B6.
After alarm is canceled, controller returns
to initial state.
L2, L3 and L7 fl ash, L4, L5, L6 light on.
Non active elements B1, B4 and B6. After
pressing unavailable button, segment
display shows "−−−"
29