7.
Score outside edges of black conductive core.
CAUTION: Do not cut bus wire strands.
8.
Peel exposed wires back from center conductive
core.
9.
Cut and remove remaining center of core, leaving
bare conductors.
CAUTION: Do not cut bus wires!
10.
Slide 1/8" (0.3cm) x 1" (2.5cm) shrink tube over each
bus wire. To shrink tubing, move heat source
continuously from side to side. While shrinking,
ensure that tubes remain against the black core.
®
© BriskHeat
Corporation. All rights reserved.
SLCBLUC-GF Ground-Fault Protected
Power Connection Kit Installation Instructions
11.
Center the 1/2" (1.3cm) x 1" (2.5cm) heat-shrinkable
tube over the end of heating cable as shown. Heat
tube evenly until it shrinks and adhesive flows out of
both ends. Shrink the tube completely. Immediately
after shrinking, pinch with pliers between wires while
tube is still hot. Hold for 10 seconds to ensure seal.
1/2"
(1.3cm)
12.
Trim the front bus wires to 1/4" (0.7cm).
7
13.
Use insulated bus wire crimps and crimp tools to
connect black and white wires to bus wires of
heating cable.
14.
Remove release paper from mastic strips, wrap one
strip of mastic around the black wire against the end
of the splice to provide a water block, then repeat for
the white wire.
1" (2.5cm)
15.
Squeeze the mastic together.
16.
Center the 5" (12.7cm) heat-shrinkable tube over the
splice. Make sure the tube extends over the end of
each heating cable and the cord. Shrink the tube
completely. Start at the middle and work toward each
end. Keep heating after the tube has shrunk to melt
mastic and adhesive inside the tube. Total heating
time should be about 3 minutes.
®
© BriskHeat
Corporation. All rights reserved.
SLCBLUC-GF Ground-Fault Protected
Power Connection Kit Installation Instructions
17.
Make sure the adhesive will appear at both ends.
Immediately after shrinking, pinch first one end of the
tube and then the other end with needle nose pliers
until the ends stay sealed.
18.
Slide one end of an insulated crimp connector over
the end of the green wire.
19.
Crimp using crimp tool.
20.
Slide 1/3" (0.74cm) x 1-1/2" (0.37cm) shrink tubes
over the ground wire, but do not shrink the tube.
8