Installing the Insert
Step 5
Gas Pressure Requirements
Minimum
5.0 inches
Inlet Pressure
Maximum Inlet
14.0 inches
Gas Pressure
Manifold
3.5 inches
Pressure
A one-eighth (1/8) inch (3 mm) N.P.T. plugged tapping is
provided on the inlet and outlet side of the gas control for a
test gauge connection to measure the manifold pressure.
Use a small flat blade screwdriver to crack open the screw
in the center of the tap. Position a rubber hose over the tap
to obtain the pressure reading.
The fireplace and its individual shut-off valve
disconnected from the gas supply piping system during
any pressure testing of the system at test pressures in
excess of one-half (1/2) psig (3.5 kPa).
The fireplace
be isolated from the gas supply piping
system by closing its individual shut-off valve during any
pressure testing of the gas supply piping system at test
pressures equal to or less than one-half (1/2) psig (3.5 kPa).
(continued)
11.0 inches
w.c.
w.c.
14.0 inches
w.c.
w.c.
10. 0 inches
w.c.
w.c.
Installation
Étape 5
Pression dentrée
minimum
Pression dentrée
maximum du gaz
Pression au
collecteur
Une dérivation de visite NPT de 3 mm est prévue sur le côté
dadmission et sur le côté de sortie de la commande de
gaz, afin dy brancher un manomètre pour mesurer la
pression du collecteur. À laide dun petit tournevis à tête
plate, casser la vis située au centre de la dérivation. Placer
une conduite en caoutchouc sur la dérivation pour mesurer
la pression.
be
Lors des mesures de pression supérieures à
3,5 kPa (1/2 psi), débrancher la conduite dalimentation de
la cheminée.
Couper lalimentation en gaz de la cheminée et fermer la
vanne de commande avant de procéder à des contrôles de
pression de lalimentation pour des pressions supérieures
à 3,5 kPa (1/2 psi).
19
(suite)
Spécifications relatives
à la pression du gaz
Col. deau
5.0 pouces
Col. deau
14.0 pouces
Col. deau
3.5 pouces
Col. deau
11.0 pouces
Col. deau
14.0 pouces
Col. deau
10.0 pouces