When this function is not selected, both contacts
(Relay A and Relay B) will activate in the event of any
alarm on the network.
DIPSWITCH RELAY OPERATION
(ACTIVATION)
Dipswitch 1=on
WRLYM-1: N/A
RLYM-1: Relay contact B
reporting only CO events
Dipswitch 2=on
Buzzer enabled
Dipswitch 3=off
Relay A latching continuously
Dipswitch 4=off
Relay B latching continuously
Dipswitch 3=on
Relay A latching for 5 seconds
Dipswitch 4=off
Relay B latching continuously
Dipswitch 3=off
Relay A latching continuously
Dipswitch 4=on
Relay B latching for 5 seconds
Dipswitch 3=on
Relay A latching for 5 seconds
Dipswitch 4=on
Relay B latching for 5 seconds
Dipswitch 5=on
Battery back-up activated
WARNING: Ensure to isolate the power prior to
operation of the dip switches.
PLEASE NOTE: When connecting to both output relay
contacts (A & B), it is advisable to install products
(to be switched upon activation of alarm) of the
same power type and not mix between high and low
voltages. This is because the resulting higher voltage
may exceed the defined SELV safe level.
IEC voltage
AC RMS
range
voltage (V)
Low voltage
50 to 300
Extra-low
< 50
voltage

TESTING

Relays should be tested by the installer at the point
of installation to ensure correct operation. Both
relays incorporate a separate test button function (as
indicated - see 'Installation' section). Pressing the test
button will activate both relay contacts accordingly.
Please note due to the unique nature of the network,
pressing the test button on a smoke, heat or CO alarm
13
DC voltage
Defining
(V)
risk
120 to 300
Electrical
shock
< 120
Low risk