Instruction Leafl et IL00402001E
Effective June 2016
Blink
Pattern
Description
0
Thermal trip/manual disconnect
Description: The breaker has detected
an overload.
Resolution: Remove excessive loads from
the circuit.
Description: The breaker has detected a
short circuit.
Resolution: Identify the location of the short
circuit and resolve.
Description: The breaker was manually
turned off.
1
Series arc
Description: A low current arc has been
detected within one of the current path-
ways. Series arcs are typically found in
worn or degraded appliance and extension
cords, poor connections in appliances or
fixtures, or in contacts within equipment.
Resolution: Identify the equipment causing
the tripping, and repair or replace.
2
Parallel arc
Description: A high current arc has been
detected between two conductors. Parallel
arcs are usually found in installed wiring
where the wire has been compromised by
a nail or screw, tight staple, and damaged
insulation.
Resolution: Locate fault location and
replace wire.
3
Short delay
Description: Short delay is an electronic
backup to the short-circuit mechanism.
Resolution: Identify the location of the short
circuit and repair.
4
Overvoltage
Description: The breaker will trip if it expe-
riences voltage of 160V rms or greater. The
breaker can be reset and the TEST button
can be pushed to verify that the breaker is
working properly.
Resolution: Investigate utility power for
imbalance in the phases or loss of neutral.
5
Ground fault
Description: Current has found an alternate
path to ground, which could cause harm to
people or property.
Resolution: Determine the location of leak-
age current and repair.
6
Self test failure
Description: The breaker continually tests
the internal electronics and software
to ensure that the arc fault detection
technology is working properly. If the self-
diagnostics fail, the breaker will trip.
Resolution: Replace the breaker.
Contact the Eaton Technical Resource Center at
1-800-326-9513 for further assistance.
Note: For Type CL (1") refer to
compatibility list (IL00304001Y).
Schéma
de
clignote-
ment
Description
0
Déclenchement thermique/déconnexion
manuelle
Description: Le disjoncteur a détecté une
surcharge.
Résolution: Retirer les charges exces-
sives du circuit.
Description: Le disjoncteur a détecté un
court-circuit.
Résolution: Identifier l'emplacement du
court-circuit et le résoudre.
Description: Le disjoncteur a été désac-
tivé manuellement.
1
Arc en série
Description: Un arc de courant faible
a été détecté dans un des trajets de
courant. Les arcs en série se produisent
généralement dans les appareils et cor-
dons d'alimentation usés ou détériorés,
les mauvaises connexions dans les appa-
reils ou dispositifs ou dans des contacts à
l'intérieur des équipements.
Résolution: Identifier l'équipement provo-
quant le déclenchement et le réparer ou
le remplacer.
2
Arc en parallèle
Description: Un arc de courant élevé a
été détecté entre deux conducteurs. Les
arcs en parallèle se produisent générale-
ment dans des câblages installés, où
un câble a été compromis par un clou
ou une vis, une agrafe et une isolation
endommagée.
Résolution: Rechercher l'emplacement de
l'anomalie et remplacer le câble.
3
Court retard
Description: Un court retard est un
blocage électronique sur le mécanisme
de court-circuit.
Résolution: Identifier l'emplacement du
court-circuit et réparer.
4
Surtension
Description: Le disjoncteur se déclenche
en cas de tension supérieure ou égale à
160 V rms. Il est possible de réarmer le
disjoncteur et d'appuyer sur le bouton
TEST pour vérifier que le disjoncteur fonc-
tionne correctement.
Résolution: Vérifier si 'alimentation
secteur comporte un déséquilibre de
phases ou une perte de neutre.
5
Mise à la terre défectueuse
Description: Le courant a trouvé une
autre trajectoire vers la terre, ce qui
peut mettre les personnes ou le matériel
en danger.
Résolution: Déterminer l'emplacement de
la fuite de courant et réparer.
6
Échec de test automatique
Description: Le disjoncteur teste en
continu les circuits électroniques
internes et les logiciels pour assurer le
fonctionnement correct de la technologie
de détection des arcs. Le disjoncteur se
déclenche en cas d'échec des diagnos-
tics automatiques.
Résolution: Remplacer le disjoncteur.
Contacter le Centre de ressources
techniques d'Eaton au 1-800-326-9513
pour une plus ample assistance.
Note: Pour le Type CL (1po) référer à la liste de
compatibilité (IL00304001Y).
Eaton Corporation
Electrical Sector
1000 Eaton Boulevard
Cleveland, OH 44122 USA
877-ETN-CARE (877-386-2273)
Eaton.com
© 2011 Eaton Corporation
All Rights Reserved
Publication No.IL00402001E / 006
June 2016
Type CH (3/4"), Type CH (3/4") Plug-on Neutral,
Type BR (1"), Type BR (1") Quick Connect Neutral™,
Type QB (1") and Type CL (1") combination arc fault
Patrón
de luces
intermi-
tentes
0
1
2
3
4
5
6
Para obtener asistencia, comuníquese con el
Centro de Recursos Técnicos de Eaton llamando
al 1-800-326-9513.
Nota: Para el Tipo CL (1") referirse a la lista de
compatibilidad (IL00304001Y).
© 2011 Eaton Corporation
Tous droits réservés
Publication No. IL00402001E / 006
Juin 2016
© 2011 Eaton Corporation
Todos los derechos reservados
Publicación No. IL00402001E / 006
Junio 2016
Descripción
Desconexión termal/manual
Descripción: El interruptor detectó una
sobrecarga.
Solución: Retirar las cargas excesivas
del circuito.
Descripción: El interruptor detectó un
corto circuito.
Solución: Identificar la ubicación del corto
circuito y resolverlo.
Descripción: El interruptor se apagó
manualmente.
Arco en serie
Descripción: Se detectó un arco de baja
corriente en una de las rutas de corriente.
Los arcos en serie se encuentran general-
mente en cables de extensión y de apara-
tos gastados o degradados, conexiones
deficientes en aparatos o dispositivos o
en contactos dentro de los equipos.
Solución: Identificar el equipo que causa
la desconexión y repararlo o reemplazarlo.
Arco en paralelo
Descripción: Se detectó un arco de
alta corriente entre dos conductores.
Los arcos en paralelo generalmente se
encuentran en el cableado instalado
donde el cable fue dañado por un clavo o
tornillo, fue ajustado muy estrechamente y
se dañó el aislamiento.
Solución: Buscar la ubicación de la falla
y reemplazar el cable.
Retardo breve
Descripción: Un retardo breve es un
respaldo electrónico del mecanismo de
corto circuito.
Solución: Identificar la ubicación del corto
circuito y repararlo.
Sobrevoltaje
Descripción: El interruptor se desconec-
tará si experimenta un voltaje mayor o
igual a 160V RMS. Se puede restablecer
el interruptor y presionar el botón TEST
(prueba) para verificar que el interruptor
esté funcionando correctamente.
Solución: Revisar la energía eléctrica en
busca de un desbalance de fases o una
pérdida de carga neutra.
Falla a tierra
Descripción: La corriente encontró una
ruta alternativa de conexión a tierra, lo
cual puede producir daños a las personas
o la propiedad.
Solución: Determinar la ubicación de la
corriente de fuga y repararla.
Falla de prueba automática
Descripción: El interruptor prueba
continuamente el sistema electrónico
interno y el software para garantizar
que la tecnología de detección de fallas
de arco funcione correctamente. Si el
diagnóstico automático falla, el interruptor
se desconecta.
Solución: Reemplazar el interruptor.