GENERAL PRODUCT INFORMATION

The probe is part of the leak alarms of LWG series, type LWG 2000 and LWG 2005.
The probe is configured for immersion in the operating medium to be identified.
The probe and indicator are connected on the basis of a connection line.
The leakage of water-endangering liquids or water that is not intended for human
consumption and/or the incursion of liquids into a containment facility are displayed
automatically on the indicator.

INTENDED USE

The probe(s) may only be used as part of the leak alarms in the LWG series, type LWG 2000
and LWG 2005.
Accordingly, the INTENDED USE of the leak detectors of the LWG series is to be taken into
account.
Please note the assembly and operating manual for the "Leak alarm type
LWG 2000", part no. 15 073 50!
Please note the assembly and operating manual for the "Leak alarm type
LWG 2005", part no. 15 074 51!
Operating media
• Waste oil
• Diesel fuel
• FAME
• Water or oil-water mixtures (+1°C to +70°C)
• Water not intended for human consumption
• Aqueous solutions of inorganic, non-oxidising salts with a pH between 6 and 8.
• other water-hazardous, non-flammable liquids with a flash point above 55 °C.
• other water-hazardous, non-flammable liquids and flammable liquids with a flash point
above > 55 °C with proof of function from the manufacturer's tests:
Immerse the probe in the operating medium to be tested. Leave in a heating cabinet at
+ 60 °C for 48 hours. Then carry out the specified FUNCTION TESTS at ambient
temperature. A certificate of the test and the result must be issued.
You will find a list of operating media with descriptions, the relevant
standards and the country in which they are used in the Internet at
www.gok-online.de/de/downloads/technische-dokumentation.
Place of operation
May not be used in potentially explosive areas.
Can cause an explosion or serious injuries.
Installation location
• If used outdoors, the probe must be positioned so that no surface water, rainwater, dirt or
airborne sand can get into the containment facility or the cable connection fitting
(part no. 15 379 00).
• Containment facilities
part no. 15 073 96
• Fuel oil
• Bio fuel oil
• Heavy heating oil
• Urea solution
• Industrial oil
• Vegetable oil
Probe
• Liquid fertiliser
(AHL, ASL, HAS)