Télécharger Imprimer la page

Berker 7531 40 07 Mode D'emploi page 18

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 29
GB
Switching actuator outputs, 6-channel and 8-channel
(outputs A5 – A8)
Switched voltage
Switched current at 230 V AC
Switching capacity
incandescent lamps
fluorescent lamps
non-compensated, cos ϕ= 0.5
parallel compensation, cos ϕ = 1 : 2 x 58 W / 14 µF
lead-lag circuit, cos ϕ = 1
Siemens electronic ballast
58 W fluorescent lamp
36 W fluorescent lamp
18 W fluorescent lamp
Technical Data
: 230 V AC
: 6 A / AC1
: 1000 W
: 500 W
3 x 36 W / 14 µF
6 x 18 W / 14 µF
: 1000 W
: 10 units
: 15 units
: 15 units
Technical Data
4-channel C-load and and 8-channel C-load switching
actuator outputs
Switched voltage
Switched current at 230 V AC
Switched current at 400 V AC
Switching capacity
incandescent, HV halogen lamps
LV halogen lamps
Tronic transformers
fluorescent lamps
non-compensated, cos ϕ = 0.5
parallel compensation, cos ϕ = 1
lead-lag circuit, cos ϕ = 1
Mercury / sodium vapour lamp
non-compensated; parallel compensation : 3680 W / 200 µF
Technical specifications subject to change
GB
: 230 V AC, 400 V AC
: 16 A / AC1; 10 A / AC3
: 10 A / AC1; 6 A / AC3
: 3680 W
: 2000 VA
: 2500 W
: 3680 W
: 2500 W / 200 µF
: 2 x 3680 W

Publicité

loading

Ce manuel est également adapté pour:

7531 40 107531 60 027531 80 017531 80 02