Télécharger Imprimer la page

UTC FLO115DABR-A Guide D'installation Et Manuel Du Propriétaire page 39

Appareil de chauffage central à air chaud

Publicité

Les langues disponibles

Les langues disponibles

The required minimum clearances for this furnace are specified
in table #1.
The furnace should be located as close as possible to the chimney to
keep vent connections short and direct. The furnace should also be
located as near as possible to the center of the air distri b uti o n system.
CAUTION
Do NOT operate furnace in a corrosive atmosphere
containing chlorine, fluorine or any other damaging
chemicals. Refer to Part 1, section 5.2.
LOCATION
Furnace
Sides
Supply plenum within 6 ft of furnace
Back
Furnace
Furnace or plenum
Top
Horizontal warm air duct within 6 ft of furnace
Bottom
Furnace (combustible floor)
Horizontally or below flue pipe
Flue pipe
Vertically above flue pipe
Front
From burner
4)
VENTING
WARNING
WARNING
!
Poison carbon monoxide gas, fire and explosion
hazard.
Read and follow all instructions in this section.
Failure to properly vent this furnace can result in
property damage, personal injury and/or death.
CAUTION
When the furnace (chimney installation) is co-vented
with other combustion appliances such as a water
heater, the allowable vent ing materials (i.e. L -Vent etc.)
for use with those appliances should also be
investigated.
The oil furnaces are certified for use with L-vent, A-vent, tile-lined and
metal-liner-tile-lined chimneys. The appliance may be installed in a
chimney of the proper size and adequate chimney base temperature
as specified in the Installation Code. The relevant excerpt from the
code is found in this section - Use it as a guide when local or national
codes do not exist.
Flue pipe sizing:
The following table is an except from the installation code and
indicates permitted flue sizes and minimum base temperatures for
circular flues in chimney with thermal resistance less than R6 (6 ft
•°F / Btu). Where a new appliance, burner, or chimney is installed,
chimney vent sizes and maximum flue-gas temperatures (measured at
TABLE #1
Minimum clearances – combustion materials (in)
APPLICATION
•hr
2
WARNING
WARNING
!
Electrical shock hazard.
This furnace is not watertight and is not designed
for outdoor installation.
installed in such a manner as to protect the
electrical components from water.
Outdoor installation would lead to a hazardous
electrical condition and to premature furnace
failure, property damage, bodily injury or death.
the chimney connector with the barometric damper shut, after 5
minutes of operation) shall comply with the table #2.
WARNING
WARNING
!
Poison carbon monoxide gas hazard
Never install a hand operated damper in the vent
pipe.
However, any Underwriters Laboratories
listed electrically operated automatic type vent
damper may be installed if desired. Be sure to
follow instructions provided with vent damper.
Read and follow all instructions in this section.
Failure to properly vent this furnace or other
appliances can result in property damage, personal
injury and/or death.
NOTES: Thermal resistance values for typical chimneys are as
follows:
•hr •°F / Btu):
2
R2 (2 ft
•hr •°F / Btu):
2
R3 (3 ft
•hr •°F / Btu):
2
R6 (6 ft
This furnace shall be
In
1"
1"
18"
1"
1"
0"
9"
9"
24"
clay-lined masonry, A-vent
metal liner in clay-lined
Masonry
metal or clay-lined masonry
•hr •°F / Btu)
2
with R4.5 (4.5 ft
insulation between liner and
masonry (e.g. 2 in. of
expanded mica or 1 3/8 in. of
high density glass fibreboard.)
5

Publicité

loading