VENTURI ADJUSTMENT
Air shutter opening has been factory set according to the chart
below:
VENTURI ADJUSTMENT CHART
FUEL
NG
P
Adjustment is required depending on fuel type, vent configuration
and altitude.
Air shutter adjustment must be done by a qualified
Closing the air shutter will cause a more yellow flame, but can lead
to carboning. Opening the air shutter will cause a more blue flame,
but can cause flame lifting from the burner ports. The flame may
not appear yellow immediately; allow 15 to 30 minutes for the final
flame colour to be established.
NOTE: If the intent is to use a portable propane bottle as the source of fuel for this appliance,
the bottle must be supported. A support (W655-0171) is available by your local Napoleon or
Continental dealer / distributor.
It is important to periodically perform a visual check of the pilot and burner flames.
Compare them to the illustrations below.
Birch Log Set
BLKO36
Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON L4M 0G8 Canada
ADJUSTMENTS
BURNER
1/8" (3.2mm)
3/16" (4.7mm)
installer!
VENTURI
AIR SHUTTER
OPENING
ORIFICE
FLAME CHARACTERISTICS
PRESSURE ADJUSTMENT
Adjust the pilot screw to provide properly sized flame. Turn in a clockwise
PILOT BURNER ADJUSTMENT
direction to reduce the gas flow.
Inlet pressure can be checked by turning screw (A) counter-clockwise
until loosened and then placing pressure gauge tubing over the test
point. Gauge should read 7" (minimum 4.5") water column for natural
gas or 13" (11" minimum) water column for propane. Check that main
THERMOCOUPLE
burner is operating on "HI".
Outlet pressure can be checked the same as above using screw (B).
Gauge should read 3.5" water column for natural gas or 10" water
column for propane. Check that main burner is operating on "HI".
AFTER TAKING PRESSURE READINGS, TIGHTEN SCREWS
FIRMLY TO SEAL. DO NOT OVER TORQUE.
LEAK TEST.
MAXIMUM INPUT RATINGS
NG
Adjust the pilot screw to provide properly sized fl ame. Turn
in a clockwise direction to reduce gas fl ow.
40,000 BTU/h
Inlet pressure can be checked by turning screw (A) counter-
clockwise until loosened and then placing pressure gauge
tubing over the test point. Gauge should read 7" (minimum 4.5")
water column for natural gas or 13" (11" minimum) water column
for propane. Check that main burner is operating on "HI".
Outlet pressure can be checked the same as above using
screw (B). Gauge should read 3.5" water column for natural
gas or 10" water column for propane. Check that main burner
is operating on "HI".
AFTER TAKING PRESSURE READINGS, TIGHTEN
SCREWS FIRMLY TO SEAL. DO NOT OVERTORQUE.
LEAK TEST
It is important to
periodically perform
a visual check of the
pilot and burner fl ames.
Compare them to the
illustrations provided.
Oak Log Set
OLKO36
• 1(866)820-8686
PILOT
BURNER
THERMOPILE
B
A
P
40,000 BTU/h
PILOT
BURNER
ELECTRODE
3/8" - 1/2"
FLAME
FLAME MUST
SENSOR
ENVELOPE UPPER
3/8" TO 1/2" OF
FLAME MUST ENVELOP
THERMOCOUPLE &
THERMOPILE
UPPER 3/8" TO 1/2" OF
FLAME SENSOR
• www.napoleon replaces.com
ADJUSTM
All
acc
Ad
con
Clo
can
mo
por
15
NO
pro
bot
A s
you
W415-1832 / A / 04.13.18