3. Intended purpose

Console for the separate wall mounting
of the electronics.
The accessories set contains:
– 1 console with 2m cable
– 4 screws and dowels
The electronics is normally mounted on the pump:

3.1 Ambient temperature

– The permissible ambient temperature is max. 40 °C
– Protection class: IP42

4. Fitting the console

The minimum distance from the hot pump
and pipes is 30 cm.

4.1 Preparation

– For hole spacings see table on page 3
and mark on wall accordingly.
– Drill 4 Ø 8 mm holes for dowels and fit dowels.
– Fasten console with 4 Ø 5× 40 mm screws.

4.2 Dismantling the electronics

Warning
Loosen the securing screw between
the electronics and pump motor.
Pull away the electronics towards
the motor axis.
Before every intervention
in the terminal box, the power supply
to the pump must be switched off.
Take care when opening the terminal
box cover. The electronics can still
have dangerous voltages for up to
10 minutes after the current has been
switched off.